Insulation Work
Pipe diameter
Flare dimension A (mm)
Flare shape
Min
Max
1/4" (6.35)
8.3
8.7
R0.4~0.8
A
45°
90
e
4
-+
3/8" (9.52)
12.0
12.4
1/2" (12.7)
15.4
15.8
5/8" (15.9)
18.6
19.1
3/4" (19)
22.9
23.3
¾
After flared the pipe, the opening part must be seal by end cover or adhesive tape to avoid duct or
exogenous impurity come into the pipe.
5.2.7 Drill holes if the pipes need to pass the wall.
5.2.8 According to the field condition to bend the pipes so that it can pass the wall smoothly.
5.2.9 Bind and wrap the wire together with the insulated pipe if necessary.
5.2.10
Set the wall conduit
5.2.11 Set the supporter for the pipe.
5.2.12 Locate the pipe and fix it by supporter
¾
For horizontal refrigerant pipe, the distance between supporters should not be exceed 1m.
¾
For vertical refrigerant pipe, the distance between supporters should not be exceed 1.5m.
5.2.13 Connect the pipe to indoor unit and outdoor unit by using two spanners.
¾
Be sure to use two spanners and proper torque to fasten the nut, too large torque will damage the
bellmouthing, and too small torque may cause leakage. Refer the following table for different pipe
connection.
Pipe Diameter
Torque
Sketch map
(kgf.cm)
(N.cm)
1/4" (6.35)
144~176
1420~1720
3/8" (9.52)
333~407
3270~3990
1/2" (12.7)
504~616
4950~6030
5/8" (15.9)
630~770
6180~7540
3/4" (19)
990~1210
9270~11860
6. Drainage pipe installation
Install the drainage pipe as shown below and take measures against condensation. Improperly installation
could lead to leakage and eventually wet furniture and belongings.
6.1 Installation principle
¾
Ensure at least 1/100 slope of the drainage pipe
¾
Adopt suitable pipe diameter
¾
Adopt nearby condensate water discharge
6.2 Key points of drainage water pipe installation
6.2.1 Considering the pipeline route and elevation
¾
Before installing condensate water pipeline, determine its route and elevation to avoid intersection with
other pipelines and ensure slope is straight.
45
Summary of Contents for ASC-60AN
Page 1: ...SERVICE MANUAL ASF 60AN ASC 60AN ON OFF SERIES ...
Page 2: ......
Page 8: ...Indoor Units Indoor Units Super slim Cassette Type 4 Ceiling Floor Type 17 3 ...
Page 14: ...Dimensions 2 Dimensions Model A H ASC 60AN 287 317 9 ...
Page 15: ...Service Space 3 Service Space 1000mm 1000mm 1000mm 1000m m 10 ...
Page 16: ...Wiring Diagrams 4 Wiring Diagrams ASC 60AN 11 ...
Page 18: ...Sound Levels 6 Sound Levels P Microphone Model Noise level dB A H M L ASC 60AN 55 50 47 13 ...
Page 21: ...Field Wiring 9 Field Wiring ASC 60AN 16 ...
Page 24: ...Dimensions 2 Dimensions Capacity Btu h A B C D E ASF 60AN 1650 675 235 1565 220 19 ...
Page 25: ...Service Space 3 Service Space 20 ...
Page 26: ...Wiring Diagrams 4 Wiring Diagrams ASF 60AN 21 ...
Page 29: ...Field Wiring 9 Field Wiring ASF 60AN 24 ...
Page 34: ...Wiring Diagrams 4 Wiring Diagrams ASF 60AN ASC 60AN 29 ...
Page 76: ...Troubleshooting f Indoor fan speed has been out of control Eb 71 ...
Page 79: ...Troubleshooting c Up down panel is not closed 74 ...
Page 91: ...MODEL ASC 60AN intdoor ...
Page 93: ...Model ASF 60AN indoor ...