Troubleshooting
2.3. Solving steps for typical malfunction
(1) For indoor unit
a. Communication malfunction between indoor and outdoor units(E1)
No
Power off, then turn on the unit 5
seconds later(reconnect the
power wire).Is the error still
displaying after several minutes?
Check whether the signal wire is
shield cable or whether the shield
cable is earthing?
Adopt shield cable/Shield
cable earthing.
Check whether the wire is correct
polarity? P to P, Q to Q, E to E?
No
Yes
Correct the connection.
No
Check if there’s any interference.
Such as too many lamps, power
transformers? Or the signal wire is
too long?
Yes
Remove interference.
Increase the capacity of anti-
interference
Yes
Check whether the signal wire is
broken?
Yes
Replace the signal wire.
Yes
Check whether the signal wires
insert on PCB well?
Pull out and insert back.
No
No
Replace indoor PCB, is the error
distinguished?
Yes
Replace the outdoor PCB.
No
67
Summary of Contents for ASC-60AN
Page 1: ...SERVICE MANUAL ASF 60AN ASC 60AN ON OFF SERIES ...
Page 2: ......
Page 8: ...Indoor Units Indoor Units Super slim Cassette Type 4 Ceiling Floor Type 17 3 ...
Page 14: ...Dimensions 2 Dimensions Model A H ASC 60AN 287 317 9 ...
Page 15: ...Service Space 3 Service Space 1000mm 1000mm 1000mm 1000m m 10 ...
Page 16: ...Wiring Diagrams 4 Wiring Diagrams ASC 60AN 11 ...
Page 18: ...Sound Levels 6 Sound Levels P Microphone Model Noise level dB A H M L ASC 60AN 55 50 47 13 ...
Page 21: ...Field Wiring 9 Field Wiring ASC 60AN 16 ...
Page 24: ...Dimensions 2 Dimensions Capacity Btu h A B C D E ASF 60AN 1650 675 235 1565 220 19 ...
Page 25: ...Service Space 3 Service Space 20 ...
Page 26: ...Wiring Diagrams 4 Wiring Diagrams ASF 60AN 21 ...
Page 29: ...Field Wiring 9 Field Wiring ASF 60AN 24 ...
Page 34: ...Wiring Diagrams 4 Wiring Diagrams ASF 60AN ASC 60AN 29 ...
Page 76: ...Troubleshooting f Indoor fan speed has been out of control Eb 71 ...
Page 79: ...Troubleshooting c Up down panel is not closed 74 ...
Page 91: ...MODEL ASC 60AN intdoor ...
Page 93: ...Model ASF 60AN indoor ...