Troubleshooting
Index 1:
1.Indoor DC fan motor(control chip is inside fan motor)
Measure the resistance value of each winding by using the tester. If any resistance value is zero, the fan
motor must have problems and need to be replaced.
NO.
Color
1
Red
2
---
3
Black
4
White
5
Yellow
6
Blue
Index2:
1. DC fan motor(control chip is inside fan motor)
Power on and when the unit is in standby, measure the voltage of pin1-pin3, pin4-pin3 in fan motor
connector. If the value of the voltage is not in the range showing in below table, the PCB must have
problems and need to be replaced.
DC motor voltage input and output
NO.
Color
Signal
Voltage
1
Red
Vs/Vm
140~380V
2
---
---
---
3
Black
GND
0V
4
White
Vcc
13.5~16.5V
5
Yellow
Vsp
0~6.5V
6
Blue
FG
15V
72
Summary of Contents for ASC-60AN
Page 1: ...SERVICE MANUAL ASF 60AN ASC 60AN ON OFF SERIES ...
Page 2: ......
Page 8: ...Indoor Units Indoor Units Super slim Cassette Type 4 Ceiling Floor Type 17 3 ...
Page 14: ...Dimensions 2 Dimensions Model A H ASC 60AN 287 317 9 ...
Page 15: ...Service Space 3 Service Space 1000mm 1000mm 1000mm 1000m m 10 ...
Page 16: ...Wiring Diagrams 4 Wiring Diagrams ASC 60AN 11 ...
Page 18: ...Sound Levels 6 Sound Levels P Microphone Model Noise level dB A H M L ASC 60AN 55 50 47 13 ...
Page 21: ...Field Wiring 9 Field Wiring ASC 60AN 16 ...
Page 24: ...Dimensions 2 Dimensions Capacity Btu h A B C D E ASF 60AN 1650 675 235 1565 220 19 ...
Page 25: ...Service Space 3 Service Space 20 ...
Page 26: ...Wiring Diagrams 4 Wiring Diagrams ASF 60AN 21 ...
Page 29: ...Field Wiring 9 Field Wiring ASF 60AN 24 ...
Page 34: ...Wiring Diagrams 4 Wiring Diagrams ASF 60AN ASC 60AN 29 ...
Page 76: ...Troubleshooting f Indoor fan speed has been out of control Eb 71 ...
Page 79: ...Troubleshooting c Up down panel is not closed 74 ...
Page 91: ...MODEL ASC 60AN intdoor ...
Page 93: ...Model ASF 60AN indoor ...