Electrical Control Function
For Ceiling & Floor:
T3
TE10
Off
On
TE11
When T3
TE10, the compressor will shut off. When T3
ψ
TE11,the compressor will restart.
1.3.3 Heating Mode
1.3.3.1 Compressor running rules:
For Duct & super-slim cassette type: Once the compressor starts up, it keeps running 7 minutes,
For Ceiling & Floor
:
Once the compressor starts up, it keeps running HEATFTIM minutes,
then it will follow the below rules:
When indoor room temp.T1 is higher than Tgap0, the compressor and outdoor fan will shut off. When T1 is
lower than Tgap0-1, the compressor and outdoor fan will start up.
Tgap0
T1-TS
On
Off
Tgap0-1
For Ceiling & Floor:Tgap0 = setting temperature-compensation.
1.3.3.2 Outdoor fan running rules:
Fan(below): The outdoor fan runs all the time.
Fan(above):
18
T4
Off
On
16
1.3.3.3 Indoor fan running rules:
When the compressor is on, the indoor fan can be set to high/med/low/auto. And the anti-cold wind function
has the priority.
59
Summary of Contents for ASC-60AN
Page 1: ...SERVICE MANUAL ASF 60AN ASC 60AN ON OFF SERIES ...
Page 2: ......
Page 8: ...Indoor Units Indoor Units Super slim Cassette Type 4 Ceiling Floor Type 17 3 ...
Page 14: ...Dimensions 2 Dimensions Model A H ASC 60AN 287 317 9 ...
Page 15: ...Service Space 3 Service Space 1000mm 1000mm 1000mm 1000m m 10 ...
Page 16: ...Wiring Diagrams 4 Wiring Diagrams ASC 60AN 11 ...
Page 18: ...Sound Levels 6 Sound Levels P Microphone Model Noise level dB A H M L ASC 60AN 55 50 47 13 ...
Page 21: ...Field Wiring 9 Field Wiring ASC 60AN 16 ...
Page 24: ...Dimensions 2 Dimensions Capacity Btu h A B C D E ASF 60AN 1650 675 235 1565 220 19 ...
Page 25: ...Service Space 3 Service Space 20 ...
Page 26: ...Wiring Diagrams 4 Wiring Diagrams ASF 60AN 21 ...
Page 29: ...Field Wiring 9 Field Wiring ASF 60AN 24 ...
Page 34: ...Wiring Diagrams 4 Wiring Diagrams ASF 60AN ASC 60AN 29 ...
Page 76: ...Troubleshooting f Indoor fan speed has been out of control Eb 71 ...
Page 79: ...Troubleshooting c Up down panel is not closed 74 ...
Page 91: ...MODEL ASC 60AN intdoor ...
Page 93: ...Model ASF 60AN indoor ...