Drainage pipe installation
6.2.2 Drainage pipe selection
¾
The drainage pipe diameter shall not small than the drain hose of indoor unit
¾
According to the water flowrate and drainage pipe slope to choose the suitable pipe, the water flowrate
is decided by the capacity of indoor unit.
Relationship between water flowrate and capacity of indoor unit
Capacity (x1000Btu)
Water flowrate (l/h)
12
2.4
18
4
24
6
30
7
36
8
42
10
48
12
60
14
According to the above table to calculate the total water flowrate for the confluence pipe selection.
For horizontal drainage pipe
(The following table is for reference)
PVC pipe
Reference value of inner
diameter of pipe (mm)
Allowable maximum water flowrate (l/h)
Remark
Slope 1/50
Slope 1/100
PVC25
20
39
27
For branch pipe
PVC32
25
70
50
PVC40
31
125
88
Could be used for confluence pipe
PVC50
40
247
175
PVC63
51
473
334
Attention: Adopt PVC40 or bigger pipe to be the main pipe.
For Vertical drainage pipe
(The following table is for reference)
PVC pipe
Reference value of inner
diameter of pipe (mm)
Allowable maximum water flowrate (l/h)
Remark
PVC25
20
220
For branch pipe
PVC32
25
410
PVC40
31
730
Could be used for confluence pipe
PVC50
40
1440
PVC63
51
2760
PVC75
67
5710
PVC90
77
8280
Attention: Adopt PVC40 or bigger pipe to be the main pipe.
6.2.3 Individual design of drainage pipe system
¾
The drainage pipe of air conditioner shall be installed separately with other sewage pipe, rainwater pipe
and drainage pipe in building.
¾
The drainage pipe of the indoor unit with water pump should be apart from the one without water pump.
6.2.4 Supporter gap of drainage pipe
¾
In general, the supporter gap of the drainage pipe horizontal pipe and vertical pipe is respectively
1m~1.5m and 1.5m~2.0m.
¾
Each vertical pipe shall be equipped with not less than two hangers.
¾
Overlarge hanger gap for horizontal pipe shall create bending, thus leading to air block.
Too long distance
Gas bag
6.2.5 The horizontal pipe layout should avoid converse flow or bad flow
46
Summary of Contents for ASC-60AN
Page 1: ...SERVICE MANUAL ASF 60AN ASC 60AN ON OFF SERIES ...
Page 2: ......
Page 8: ...Indoor Units Indoor Units Super slim Cassette Type 4 Ceiling Floor Type 17 3 ...
Page 14: ...Dimensions 2 Dimensions Model A H ASC 60AN 287 317 9 ...
Page 15: ...Service Space 3 Service Space 1000mm 1000mm 1000mm 1000m m 10 ...
Page 16: ...Wiring Diagrams 4 Wiring Diagrams ASC 60AN 11 ...
Page 18: ...Sound Levels 6 Sound Levels P Microphone Model Noise level dB A H M L ASC 60AN 55 50 47 13 ...
Page 21: ...Field Wiring 9 Field Wiring ASC 60AN 16 ...
Page 24: ...Dimensions 2 Dimensions Capacity Btu h A B C D E ASF 60AN 1650 675 235 1565 220 19 ...
Page 25: ...Service Space 3 Service Space 20 ...
Page 26: ...Wiring Diagrams 4 Wiring Diagrams ASF 60AN 21 ...
Page 29: ...Field Wiring 9 Field Wiring ASF 60AN 24 ...
Page 34: ...Wiring Diagrams 4 Wiring Diagrams ASF 60AN ASC 60AN 29 ...
Page 76: ...Troubleshooting f Indoor fan speed has been out of control Eb 71 ...
Page 79: ...Troubleshooting c Up down panel is not closed 74 ...
Page 91: ...MODEL ASC 60AN intdoor ...
Page 93: ...Model ASF 60AN indoor ...