00 (Hex)
1E (Hex)
CB (Hex)
07 (Hex)
00 (Hex)
04 (Hex)
02 (Hex)
Data Register-2 Low Byte
Byte Count
CRC High
Data Register-1 Low Byte
Data Register-2 High Byte
Data Register-1 High Byte
}
Voltage 2 *
(3X Address 0x0002)
Power Factor 1 *
(3X Address 0x001E)
}
CRC Low
Reading Parameter data through User Assignable Registers:
In assigning query Voltage2 and Power Factor1 parameters were assigned to 0x200 and
0x201(Table10) which will point to user assignable 3x registers 0x200 and 0x202 (Table 9).
So to read Voltage2 and Power Factor1 data reading query should be as below.
Device Address
Function Code
Start Address High
Start Address Low
Number of Register Hi
Number of Register Lo
CRC Low
CRC High
01 (Hex)
10 (Hex)
02 (Hex)
00 (Hex)
00 (Hex)
02 (Hex)
40 (Hex)
70 (Hex)
Response :
53