Simpson Amik 300 Operating Manual Download Page 54

02

08

40521

265

Mapped Add for register #0x0210

09

02

0A

02

40522

266

40523

267

Modbus start Address (Hex)

Address

(Register)

Parameter

  Number.

Mapped Register

High Byte

Low Byte

0B

02

0C

02

0D

02

0E

02

0F

02

10

02

11

02

12

02

13

02

40524

268

40525

269

40526

270

40527

271

40528

272

40529

273

40530

274

40531

275

40532

276

Example :

Assigning parameter to user assignable registers

To access the voltage2 (3X address 0x0002) and Power Factor1 (3X address 0x001E)
through user assignable register assign these addresses to  4x register (Table 10 ) 0x0200
and 0x0201 respectively.

Assigning Query:

01 (Hex)

Device Address

10 (Hex)

Function Code

02 (Hex)

Starting Address Hi

00 (Hex)

Starting Address Lo

00 (Hex)*

Number of Register Hi

02 (Hex)*

Number of Register Lo

52

Mapped Add for register #0x0212

Mapped Add for register #0x0214

Mapped Add for register #0x0216

Mapped Add for register #0x0218
Mapped Add for register #0x021A

Mapped Add for register #0x021C

Mapped Add for register #0x021E
Mapped Add for register #0x0220
Mapped Add for register #0x0222
Mapped Add for register #0x0224

Mapped Add for register #0x0226

Summary of Contents for Amik 300

Page 1: ...ion for this product However Company has no control over the field conditions which influence product installation It is the user s responsibility to determine the suitability of the installation meth...

Page 2: ...Cover Page 2...

Page 3: ...ction screen 3 2 1 1 System type 3 2 1 2 Potential transformer Primary value 3 2 1 3 Potential transformer Secondary value 3 2 1 4 Current transformer Primary value 3 2 1 5 Current transformer Seconda...

Page 4: ...t Option selection screen menu 3 2 3 1 Resetting Parameter 8 Number of Interruption 7 On Hour 6 Run Hour 5 Phase Rotation Error screen 9 Analog Output 3 2 5 Brightness Contrast 4 Touch screen calibrat...

Page 5: ...configure the product setting LINE NEUTRAL V OLTAGE VOLTAGE MAIN VL2 VL2 VL2 VL2 V V V V V 0 000 0 000 0 000 LINE NEUTRAL V OLTAGE VOLTAGE MAIN VL2 VL2 VL2 VL2 V V V V V 0 000 0 000 0 000 LINE NEUTRAL...

Page 6: ...4 wire only Amps Amps Measurement Active Import Energy 8 Digit resolution kWh kWh Active Export Energy 8 Digit resolution Active Power System Phase 4 wire only Reactive Power System Phase 4 wire only...

Page 7: ...KW KW KW Hours Hours Counts Measurement Amps Current Demand KVA Demand KVA I1 THD I2 THD V1 THD V2 THD V3 THD I3 THD System Voltage THD System Current THD Pictorial representation of Phaser Diagram 4...

Page 8: ...een 4 Pictorial VOLTAGE MAIN VL2 0 000 VOLTAGE MAIN VL2 0 000 VOLTAGE MAIN VL2 0 000 MAIN Inductive Capacitive Inductive Capacitive 0 90 180 0 270 0 0 0 VL1 VL2 VL3 IL1 IL2 IL3 3 2 1 0 000 0 000 0 000...

Page 9: ...GE VOLTAGE MAIN VL2 VL2 VL2 VL2 V V V V V 0 000 0 000 0 000 LINE NEUTRAL VOL TAGE VOLTAGE MAIN VL2 VL2 VL2 VL2 V V V V V 0 000 0 000 0 000 LINE NEUTRAL VOL TAGE VOLTAGE MAIN VL2 VL2 VL2 VL2 V V V V V...

Page 10: ...u list For 4 wire only of Voltage Waveform Only accessed LINE NEUTRAL VOL TAGE VOLTAGE MAIN VL2 VL2 VL2 VL2 V V V V V 0 000 0 000 0 000 LINE NEUTRAL VOL TAGE VOLTAGE MAIN VL2 VL2 VL2 VL2 V V V V V 0 0...

Page 11: ...POWER MAIN L2 L1 L3 1 000 1 000 1 000 LINE NEUTRAL VOL TAGE VOLTAGE MAIN VL2 VL2 VL2 VL2 V V V V V 0 000 0 000 0 000 LINE NEUTRAL VOL TAGE VOLTAGE MAIN VL2 VL2 VL2 VL2 V V V V V 0 000 0 000 0 000 LIN...

Page 12: ...0 0 000 LINE NEUTRAL VOL TAGE VOLTAGE MAIN VL2 VL2 VL2 VL2 V V V V V 0 000 0 000 0 000 LINE NEUTRAL VOL TAGE VOLTAGE MAIN VL2 VL2 VL2 VL2 V V V V V 0 000 0 000 0 000 ACTIVE ENERGY EXPORT ENERGY MAIN 0...

Page 13: ...OF INTERRUPTIONS CT SECONDARY DEMAND NOISE CUTOFF AUTO SCROLL Sec 3 2 1 5 Sec 3 2 1 7 INTEGRATION TIME LOW CURR POWERFACTOR SEQUENCE PHASE SYSTEM POWER THD VOLTAGE AND CURRENT Sec 3 2 2 3 VOLTAGE THD...

Page 14: ...rameter selection Acc To Table 2 DEMAND Sec 3 2 1 6 INTEGRATION TIME RESETMAXVOLTAGE CURRENT RESETMINVOLTAGE CURRENT RESETRUN HOUR ON HOUR RESETAUXINTERRUPTCOUNT Select any option by RESETALL PASSWORD...

Page 15: ...ake the User into the Password Protection Stage Section 3 1 After touching SETUP icon Password protection screen is displayed Screen consists of 0 to 9 digit input keypad for entering the password ver...

Page 16: ...ASSWORD ACCEPTED If Entered password is wrong then Password Rejected is displayed on screen user need to re enter the password Password Incorrect SETUP PASSWORD REJECTED After wrong password is entere...

Page 17: ...W PASSWORD PASSWORD PASSWORD CHANGED After entering new password user needs to touch After confirming PASSWORD CHANGED is displayed on screen which ensures successful changing of the password ENTER Ne...

Page 18: ...IONS 3 2 5 BRIGHTNESS CONTRAST 3 2 1 1 System Type LINE NEUTRAL VOL TAGE VL2 VL2 VL2 VL2 0 000 LINE NEUTRAL VOL TAGE VL2 VL2 VL2 VL2 0 000 LINE NEUTRAL VOL TAGE VL2 VL2 VL2 VL2 0 000 SYSTEM TYPE 3 PHA...

Page 19: ...L to 692 8 KVL L 3 2 1 3 Potential Transformer secondary Value The value must be set to the nominal full scale secondary voltage which will be obtained from the the Transformer when the potential tran...

Page 20: ...E NEUTRAL VOL TAGE LINE NEUTRAL VOL TAGE PT SECONDARY INVALID VALUE In case presently displayed Current Transformer Primary Value together with the Potential Transformer Primary Value results in a max...

Page 21: ...0 000 CT SECONDARY 1 AMPERE 5 AMPERE MAIN MAIN MAIN MAIN MAIN MAIN OK BACK Touch on key will confirm the setting Touching the key will keep the old selected setting and will return to previous menu OK...

Page 22: ...VL2 LINE NEUTRAL VOL TAGE VL2 VL2 VL2 LOW CURRENT NOISE CUTOFF 0 MILLI AMPERE 30 MILLI AMPERE MAIN MAIN MAIN MAIN MAIN MAIN OK BACK and will return to previous menu Touching the key will keep the old...

Page 23: ...ep the old selected setting and will return to previous menu BACK 3 2 1 10 ENERGY DIGIT RESET COUNT ROLLOVER COUNT LINE NEUTRAL VOL TAGE VL2 VL2 VL2 LINE NEUTRAL VOL TAGE VL2 VL2 VL2 LINE NEUTRAL VOL...

Page 24: ...options 2400 4800 9600 19200 Bauds are displayed on screen Touching radio button in front of particular option will select that option Touch on key will confirm the setting OK LINE NEUTRAL VOL TAGE VL...

Page 25: ...Parameter These screens allow the users to reset all the parameters eg Energy Min Max Demand Run hour On hour No of Interrupts Touching down key scrolls list in upward direction 3 2 3 Reset Parameter...

Page 26: ...put Option selection menu After entering in the OUTPUT OPTIONS List of following parameters will be displayed 3 2 4 3 ANALOG 1 Model 301 only 3 2 4 4 ANALOG 2 Model 301 only 24 NO 3 2 4 3 Parameter se...

Page 27: ...L TAGE VOLTAGE MAIN VL2 VL2 VL2 VL2 V V V V V 0 000 0 000 LINE NEUTRAL VOL TAGE VOLTAGE MAIN VL2 VL2 VL2 VL2 V V V V V 0 000 0 000 VOLTAGE MAIN BRIGHTNESS CONTRAST BACK DEFAULT OK DEFAULT CONTRAST BRI...

Page 28: ...TAGE VOLTAGE MAIN VL2 VL2 VL2 VL2 V V V V V 0 000 0 000 0 000 LINE NEUTRAL VOL TAGE VOLTAGE MAIN VL2 VL2 VL2 VL2 V V V V V 0 000 0 000 0 000 LINE NEUTRAL VOL TAGE VOLTAGE MAIN VL2 VL2 VL2 V V V V V 0...

Page 29: ...INPUT ABSENT PLEASE CHECK YOUR CONNECTIONS 6 Run Hour This Screen shows the total no of hours the load is connected Even if the Auxiliary supply is interrupted count of Run hour will be maintained in...

Page 30: ...000 0 000 SYSTEM ON HOUR SYSTEM MAIN 000005 18 hrs 8 Number of Interruption This Screen Displays the total no of times the Axillary Supply was Interrupted Even if the Auxiliary supply is interrupted c...

Page 31: ...sent any one of the measured and displayed Parameters All settlings are user configurable via the user interface screen See Analog o p selection section 3 2 4 3 section 3 2 4 4 for details Note Refer...

Page 32: ...ter Parameter 0 1 2 INPUT VOLTAGE L2 2 3 INPUT VOLTAGE L3 None 4 INPUT CURRENT IL1 3P 4W 3P 3W Range 0 100 0 100 0 100 0 100 5 INPUT CURRENT IL2 6 INPUT CURRENT IL3 0 100 0 100 0 120 9 9 9 9 9 9 9 9 9...

Page 33: ...0 0 1800 1800 0 1800 1800 0 1800 1800 0 1800 0 120 0 120 0 120 0 120 22 VOLTAGE AVG 24 CURRENT AVG 27 ACTIVE POWER SUM 29 APPARENT POWER SUM 31 REACTIVE POWER SUM 32 POWER FACTOR AVG 34 PHASE ANGLE AV...

Page 34: ...LTAGE L12 102 INPUT VOLTAGE L23 103 INPUT VOLTAGE L31 113 NEUTRAL CURRENT 0 100 0 100 0 100 0 100 0 120 0 120 0 100 0 100 9 9 9 9 9 9 9 9 9 8 9 8 9 8 9 8 Note Parameters 1 2 3 are L N Voltage for 3P 4...

Page 35: ...e and be at both ends of the line The cable should be terminated at each end with a 120 ohm 1 4 Watt min resistor RS 485 network supports maximum lenght of 1 2km Including the Master a maximum of 32 i...

Page 36: ...or 2 bits if no parity Byte format Communication Baud Rate is user selectable from the front panel between 2400 4800 9600 19200 bps Exception Cases An exception code will be generated when the instrum...

Page 37: ...arameters To read parameter Volts 3 Start address 04 Hex Number of registers 02 Note Number of registers Number of parameters x 2 Each Query for reading the data must be restricted to 20 parameters or...

Page 38: ...Low Byte Least significant 8 bit of Data register 1 of the parameter requested Data register 2 High Byte Most significant 8 bits of Data register 2 of the parameter requested Data register 2 Low Byte...

Page 39: ...ent Ave 00 2E 30049 25 Current Sum 00 30 30051 26 Watts Ave 00 32 30053 27 Watts Sum 00 34 30055 28 VA Ave 00 36 30057 29 VA Sum 00 38 30059 30 VAr Ave 00 3A 30061 31 VAr Sum 00 3C 30063 32 PF Ave 00...

Page 40: ...Byte Low Byte 3P 4W 3P 3W 30099 30101 30103 30105 30097 30107 30133 30085 30087 30089 30091 30093 30095 30135 30141 30143 30201 50 51 52 53 49 54 67 43 44 45 46 47 48 68 71 72 101 VA Demand VA Max Dem...

Page 41: ...CC CE D0 D2 D4 D6 D8 DA DC E0 E2 E4 E6 9 9 9 9 9 9 9 9 9 9 9 9 9 9 8 8 9 9 9 9 9 9 9 9 8 9 9 9 Note Parameters 1 2 3 are L N Voltage for 3P 4W L L Voltage for 3P 3W Each setting is held in the 4X reg...

Page 42: ...ister Lo Least significant 8 bits of Number of registers requested Note Two consecutive 16 bit register represent one parameter Device Address Function Code Start Address High Start Address Low Number...

Page 43: ...a register 2 High Byte Most significant 8 bits of Data register 2 of the parameter requested Note Two consecutive 16 bit register represent one parameter Data register 2 Low Byte Least significant 8 b...

Page 44: ...r 1 Low Byte Least significant 8 bits of Data register 1 of the parameter requested Data register 2 High Byte Most significant 8 bits of Data register 2 of the parameter requested Note Two consecutive...

Page 45: ...rameter Modbus Start Address Hex Low Byte High Byte 40007 4 Sys Voltage Read Write R 40009 5 Sys Current R 6 Sys Type 40011 R Wp 40019 40015 8 RS 485 Set up Code R Wp 40021 11 Node Address 40025 13 Mi...

Page 46: ...yte H High Byte Read Write 00 24 40037 19 System Power R 40041 21 28 Register Order Word Order 22 40043 CT Secondary PT Secondary 2A 2C 40045 23 46 40071 36 Password 4E 40079 40 30mA Noise Current Eli...

Page 47: ...d displays System Voltage 40009 System Current This address is read only and display System Current This address is used to set the System type Write one of the follow value to this address 2 3 Phase...

Page 48: ...s register address is used to set Device address between 1 to 247 40025 Min Reset This address is used to reset the Min parameters value Write Zero value to this register to reset the Min parameters W...

Page 49: ...r for all ModBus transaction invoving floating point numbers This address allows the user to set CT Primary Value The maximum settable value is 9999 also depends on the per phase 666 6MVA Restriction...

Page 50: ...lock is present if this location is read it will return zero 2 If Password lock is absent if this location is read it will return One 3 If password lock is present to disable this lock first send vali...

Page 51: ...ity Stop Bit Decimal value 01 02 01 01 15 08 09 10 ODD 9600 4800 4800 NONE NONE 4800 4800 2400 2400 2400 2400 NONE NONE ODD EVEN ODD EVEN 02 01 01 01 02 01 01 01 01 11 04 05 06 07 00 01 02 03 NOTE Cod...

Page 52: ...pping them to adjacent address in the user assignable registers area The actual address of the parameters 3X registers addresses which are to be assessed via address 0x200 to 0x226 are specified in 4x...

Page 53: ...517 261 02 05 40518 262 06 40519 263 02 07 40520 264 00 40513 257 Mapped Add for register 0x0200 02 02 Modbus Start Address Hex Address Register Parameter Number Mapping Register High Byte Low Byte 51...

Page 54: ...dress 0x001E through user assignable register assign these addresses to 4x register Table 10 0x0200 and 0x0201 respectively Assigning Query 01 Hex Device Address 10 Hex Function Code 02 Hex Starting A...

Page 55: ...h User Assignable Registers In assigning query Voltage2 and Power Factor1 parameters were assigned to 0x200 and 0x201 Table10 which will point to user assignable 3x registers 0x200 and 0x202 Table 9 S...

Page 56: ...assignable register Number of register Hi Most significant 8 bits of Number of registers requested Number of register Lo Least significant 8 bits of Number of registers requested Note Two consecutive...

Page 57: ...16 bit 0x203 16 bit 0x202 16 bit 0x204 16 bit 0x205 16 bit 0x206 16 bit 0x 207 16 bit 0x224 16 bit 0x225 16 bit 0x226 16 bit 0x227 16 bit 0x200 0x202 0x204 0x206 0x224 0x226 0x200 0x201 0x202 0x203 0...

Page 58: ...s are mapped data can be acquired by using User assignable data register Starting address i e to access data of Voltage2 Power factor1 Wh import Frequency send query with starting address 0x200 with n...

Page 59: ...unting is by four side clamps slide the side clamps through side slot till side clamp gets firmly locked in a groove Refer fig Consideration should be given to the space required behind the instrument...

Page 60: ...ity this product must be installed by a qualified engineer abiding by any local regulations 2 Voltages dangerous to human life are present at some of the terminal connections of this unit Ensure that...

Page 61: ...restore correct operation The Current inputs of these products are designed for connection in to systems via Current Transformers only where one side is grounded 13 2 Case Dimension and Panel Cut Out...

Page 62: ...ry Supply The instrument should ideally be powered from a dedicated supply however it may be powered from the signal source provided the source remains within the limits of the chosen auxiliary voltag...

Page 63: ...uous input current 120 of Rated Value Nominal input current burden 0 6VA approx per phase Max short duration current input 20 xRated Value 1s application repeated 5 times at 5 min intervals Auxiliary...

Page 64: ...parant Energy r 1 0 of range Accuracy 1 Re Active Energy r 1 0 of range 62 Current 5 120 of Rated Value Angle r 1 of range Analog Output r 1 of Output end value Total Harmonic Distortion Neutral Curre...

Page 65: ...nge Active Power 0 2 of range Re Active Power 0 2 of range Apparent Power Re Active Energy Apparant Energy 0 2 of range Power Factor 1 of Unity Angle 1 of range Analog Output 1 of Output end value Tot...

Page 66: ...Value Rated Value 10 20 to 70 Voltage Current Input frequency Temperature Auxiliary supply voltage Auxiliary supply frequency Rated Value 10 Rated Value 10 Temperature Coefficient 0 025 C for Voltage...

Page 67: ...withstand test between circuits and accessible surfaces Environmental 20 to 70 C 30 to 80 C 0 90 RH 3 minute minimum 15g in 3 planes 10 55 Hz 0 15mm amplitude IP 54 as per IEC 60529 Operating temperat...

Page 68: ...ModBus RS 485 Protocol 19200 9600 4800 or 2400 Baud Rate Programmable Odd or Even with 1 stop bit Parity Or None with 1 or 2 stop bits Analog Output Option Linear 4 20mA dc into 0 500 ohm Uni directi...

Page 69: ...67 16 Connection for Optional RS 485 Analog Output rear view of the instrument 1 RS 485 Two Analog Output A1 A2 Gnd 4 20 mA B A Gnd RS 485 Gnd...

Page 70: ...h memo Invoice This warranty entitles you to bring the meter accessories at your cost to the nearest stockist dealer collect it after repairs NO TRANSPORTATION CHARGE WILL BE REIMBURSED The warranty i...

Page 71: ...any and if you notice transit damage then you must obtain the insurance surveyor report and forward it Thank you Scope of supply 1 Side Clamp 2 Connecters 3 User Manual To be filled by authorised deal...

Page 72: ...rmine the suitability of the installation method in the user s field conditions Company only obligations are those in Company standard Conditions of Sale for this product and in no case will Company b...

Reviews: