Address
Parameter
Description
40045
PT secondary
This address is used to read and write the PT secondary value.
Ref Table for the range of PT secondary settable value in
Section 3.2.1.3
40043
CT secondary
This address is used to read and write the CT secondary value
write one of the following values this address.
1=1A CT secondary
5=5A CT secondary
writing any other value will return an error.
48
40071
Password
This address is used to set & reset the password.
Valid Range of Password can be set is 0000 - 9999.
1) If password lock is present & if this location is read it will
return zero.
2) If Password lock is absent & if this location is read it will
return One.
3) If password lock is present & to disable this lock
first send valid password to this location then write “0000”
to this location.
4) If password lock is present & to modify 4X parameter
first send valid password to this location so that 4X parameter
will be accessible for modification.
5) If for in any of the above case invalid password is sent then
meter will return exceptional error 2.
40079
30mA Noise
current
Elimination
This address is used to activate or de-activate the 30 mA noise
current elimination write
0-Deactivate
30 (Decimal)-Activate
Writing any other value will return an error.