background image

Simplex Time Recorder Co.

7

S4100-0025 (EN54)  5/99

Audio Amplifiers 

(supervisory current is with “switch to battery” selected)

4100/4120-

Description

LPC Status

Quantity

Standby

Alarm

Module Size

0251

25 VRMS, 25 W, without Power Supply

36 mA

2.2 A

2” Internal

0263

25 VRMS, 100 W, with 230 VAC Power
Supply

(3)

As Required

68 ma

8.75 A

8” Internal

Audio Equipment Options

4100/4120-

Description

LPC Status

Quantity

Standby

Alarm

Module Size

0254

Microphone and Enclosure

3 mA

7 mA

0255

Master Phone

(3)

22 mA

142 mA

4” Retainer

0206

Redundant Tone Generator

45 mA

45 mA

––

0215

Phone Riser Terminal Board

0220

Standard Message Set (Custom
Messages are Available)

N.A.

As Required

Not applicable

Annunciation Equipment

4100/4120-

Description

LPC Status

Quantity

Standby

Alarm

Module Size

0301

64/64 LED/Switch Controller, Internal

(2)

15 mA

260 mA

0302

24 Point I/O Graphic Interface, Internal

N.A.

34 mA

75 mA

2” Internal

0431

Eight Red LED Module

0432

16 Red/Yellow LED Module

0433

8/8 Momentary Switch/Yellow LED
Module

0434

8/16, 3 Position Maintained
Switch/Yellow-Yellow LED Module

0435

8/16 Momentary Switch/LED Module

(2)

As Required

Not applicable

2” Retainer

Network Equipment

Model

Description

LPC Status

Quantity

Standby

Alarm

Module Size

4120-6014

Modular Network Interface Board

35 mA

35 mA

2” Internal

4120-0142

Wired Media Card

40 mA

40 mA

4120-0143

Fiber Optic Media Card

N.A.

As Required

25 mA

25 mA

N.A.

Cabinets and Accessories

4100/4120-

Description

LPC Status

Quantity

Standby

Alarm

Module Size

2052

Four Unit

2053

Six Unit

with Glass Door

2062

Four Unit

2063

Six Unit

with Solid Door

Choose One Per

Cabinet

2975-9405

Four Unit Beige Cabinet, CE Compliant

2975-9406

Six Unit Beige Cabinet, CE Compliant

(2)

Choose One Per

Cabinet

2975-9801

Semi-Flush Trim

N.A.

As Required

Not applicable

Remote Mount Options

4100/4120-

Description

LPC Status

Quantity

Standby

Alarm

Module Size

4604-9202UK

Remote LCD Panel

One maximum if

required 

(see page 4)

60 mA

200

see p. 4

7401*

24 Point Graphic Interface Module,
Remote

42 mA +

switch loads*

78 mA +

outputs*

7402*

64/64 LED/Switch Controller, Remote

67 mA +

switch loads*

285 mA fully

loaded*

6 1/2” x12 1/4”

(165 x 311 mm)

7403*

32 Point LED Driver Module, Remote

7404*

32 Point Switch Input Module, Remote

current is included

with control module

3 1/4” x 12 1/4”

(83 x 311 mm)

0440

Remote Microphone Enclosure

3 mA

7 mA

0441

Remote Phone

 N.A.

As Required

N.A.

4” Retainer

(2)

 LPC Approval pending.

(3)

 Tested by LPC to verify that no detrimental effect occurred to mandatory EN54 functions.

* Refer to Simplex document S4100-0005 for additional information.

 Product Selection 

(Continued)

Summary of Contents for TrueAlarm 4100 Series

Page 1: ...MAL PRESS RESET KEY SYSTEM FAULT POWER SITE SPECIFIC PROGRAMMABLE KEYS LEDS RESET PANEL SILENCE FIRE ALARM REVIEW ALARMS FAULT REVIEW FAULTS SOUNDER FAULT DISABLED DISABLE ENABLE SOUNDERS SOUNDERS SILENCED DISABLEMENT REVIEW DISABLED ZONES SOUNDER SILENCE RESOUND System is Normal 09 36 24 MON 05 APR 1999 4100 FIRE ALARM CONTROL 4100 4120 Series Control and Indicating Equipment shown as a 6 unit pa...

Page 2: ...AULTS FAULT DISABLE ENABLE SOUNDERS SOUNDER FAULT DISABLED SOUNDER SILENCE RESOUND SOUNDERS SILENCED REVIEW DISABLED ZONES DISABLEMENT NEXT PREV System is Normal 09 36 24 MON 05 APR 1999 4 X 40 LCD READOUT LED backlighted during normal conditions and abnormal operating conditions provides up to 40 characters for custom label information EXTENDED FUNCTION KEYPAD accessible with door open select and...

Page 3: ...rammed for temporal code or march time code RS 232 Dual Port Communication Module Up to four additional RS 232 modules total Each port can be vectored by event category Auxiliary Control Relays Built in fuse protection per contact Feedback tracks on off status of remote devices 4100 3001 four CPU controlled relays DPDT contacts rated for 2 A 24 VDC 4100 3002 four CPU controlled relays DPDT contact...

Page 4: ... to 830 Hz in 2 5 seconds recommended for fire alarm and no other purpose High Low Free running signal with a high frequency of 750 Hz for 100 msec and a low frequency of 500 Hz for 400 msec Horn Continuous 500 Hz tone primarily used for coded systems Chime 600 Hz fundamental tone with a 1 5 sec duration used as a free running tone or for coded operation Beep 500 Hz tone of 0 7 sec on 0 7 sec off ...

Page 5: ...des routing and pre amplification of digitized alarm tones and voice messages Actual tones and voice messages are digitally recorded and stored in the audio control board s message memory When called upon an integral Voice Tone Generator VTG recreates the audio waveforms of the prerecorded voice tone messages with completely natural sound The Audio Control board receives instructions from the Mast...

Page 6: ...e 3001 Four Relays 2A with Feedback 15 mA 75 mA 2 Internal 3002 Four Relays 10A with Feedback N A 15 mA 175 mA 4 Internal 3003 Eight Relays 3A with Feedback 2 As Required 25 mA 280 mA 2 Internal Power Supply Options 4100 4120 Description LPC Status Quantity Standby Alarm Module Size 0157 8 A Intelligent Power Supply with Charger 230 VAC 6 Internal 0158 8 A Power Supply 230 VAC 0164 Temperature Com...

Page 7: ...antity Standby Alarm Module Size 4120 6014 Modular Network Interface Board 35 mA 35 mA 2 Internal 4120 0142 Wired Media Card 40 mA 40 mA 4120 0143 Fiber Optic Media Card N A As Required 25 mA 25 mA N A Cabinets and Accessories 4100 4120 Description LPC Status Quantity Standby Alarm Module Size 2052 Four Unit 2053 Six Unit with Glass Door 2062 Four Unit 2063 Six Unit with Solid Door Choose One Per ...

Page 8: ... 4 654 mm 6 3 4 171 mm 26 3 8 670 mm 7 3 4 197 mm 3 3 4 95 mm See chart 3 76 mm 2 1 4 57 mm Installation Detail Side View IMPORTANT Distance between close coupled dual cabinets must be no less than 3 inches 76 mm and no more than 24 inches 610 mm Input Power Requirements Mains Input 230 VAC base models 1 A maximum Mains Input with 230 VAC expansion power supply 2 A maximum Mains Input 4100 0263 10...

Reviews: