Operator Interaction
The illustration below identifies the LCD readout and
the primary operator indicators and switch functions.
When the internal access door is lowered, the additional
keypad shown is available for extended operator
functions. Some of the features include:
•
Bright LED indicators and LCD alphanumeric
information for accurate status presentation
•
Nomenclature that is provided by insert, allowing the
terminology to be revised to suit local language
needs
•
Four site-specific programmable LEDs and switch
keys for use as required by the individual location
•
Typical LCD information is displayed in sequence:
Line 1:
First zone in alarm/Menu
Line 2:
Menu information
Line 3:
Most recent zone in alarm
Line 4:
Total event counts
Password Access
Four levels of password protection are available.
Typical access divisions are per the following:
Operation
Level
View software revision, test indicators
Access alarmed zones not shown
Display suppressed faults or disablements
1
Silence local sounder
Reset latching fault conditions
Silence fire alarm sounders
Resound fire alarm sounders
Initiate reset process
Disable/enable points, zones, or outputs
Set time and date, View historical logs
2
Clear historical logs, Manually control points and lists
3
Disconnect or adjust main or standby power
Modify program contents (EXEC)
Alter site-specific data (CFIG)
4
Simplex Time Recorder Co.
2
S4100-0025 (EN54) 5/99
SYSTEM
FAULT
POWER
ZN
1
SIG
2
AUX
3
FB
4
IO
5
MAP
6
P
7
A
8
ZONE
9
NET
-
FUNC
0
DEL
ENTER
CLR
MENU
SITE SPECIFIC PROGRAMMABLE KEYS/LEDS
RESET
PANEL SILENCE
REVIEW
ALARMS
FIRE
ALARM
REVIEW
FAULTS
FAULT
DISABLE/ENABLE
SOUNDERS
SOUNDER
FAULT/DISABLED
SOUNDER
SILENCE/RESOUND
SOUNDERS
SILENCED
REVIEW
DISABLED
ZONES
DISABLEMENT
NEXT
PREV
*** System is Normal ***
09:36:24 MON 05-APR-1999
4 X 40 LCD READOUT, LED
backlighted during
normal conditions and abnormal operating
conditions, provides up to 40 characters for custom
label information
EXTENDED FUNCTION KEYPAD
(accessible
with door open) select and scroll through display
prompts for locating additional system information,
performing maintenance functions
YELLOW FAULT LED
flashes
when a new fault event is received,
REVIEW FAULTS KEY
steps
through fault events
YELLOW DISABLEMENT LED
flashes when a new disablement
event is received,
REVIEW
DISABLED ZONES KEY
steps
through disabled zones
YELLOW SOUNDER FAULT LED
flashes when there is a fault
on a sounder circuit and turns on steady when a sounder circuit
is disabled,
DISABLE/ENABLE SOUNDERS KEY
allows all
sounders to be disabled simultaneously
YELLOW SOUNDERS SILENCED LED
turns
on to indicate that the sounder points have been
turned off,
SOUNDER SILENCE/RESOUND
KEY
silences the sounders when on and will
resound them when pressed again
RESET KEY
initiates system reset process
PANEL SILENCE KEY
turns off the local sounder
YELLOW SYSTEM FAULT LED
turns on to indicate a system fault
GREEN POWER LED
turns on whenever the c.i.e. is powered,
either mains or battery
FOUR PROGRAMMABLE
SWITCHES WITH YELLOW
LEDs
provide custom operations
labeling (labels insert into a
pocket)
RED FIRE ALARM LED
flashes when a
new alarm event is received and
REVIEW
ALARMS KEY
steps through alarm events
STATUS INDICATOR LEDs
provide system status indications
in addition to LCD information, LEDs flash to indicate the
condition and change to steady on after one minute
Operator Control Panel Functions