Master Controller Module

The 4100/4120-7014 Master Controller Board provides
system control, synchronization, and supervision of all
modules, continuously scanning each module for status
changes. Features include:

 

Operator’s Panel

 

with LCD and operator keys

 

General Fault Output

 

General Alarm Output,

 form “C” contact output

 

RS-232 Dual Port Communications Module,

one port is dedicated to control the user interface
panel, one port is unassigned (can be connected to
remote LCD Annunciator 4604-9202UK)

 

Battery Charger

 

for up to 110 Ah Batteries

 

Batteries up to 42 Ah may be mounted in the bottom
of the control cabinet

 

Batteries larger than 42 Ah mount external to main
control cabinet

 

Intelligent Power Supply:

 

Two isolated outputs of 4 Amps each at 28.5 VDC
when mains powered (24 VDC nominal during
battery operation)

 

Tap “B” provides 4 A for general purpose sounder
circuits and control power

 

Tap “A” provides 2 A (typical) for sounder circuits
controlling “clean” loads with controlled inrush
current and proper transient suppression (actual
available power depends on total system power
requirements)

Optional Modules Description

 

Conventional Zone Circuits:

 

Eight circuit zone modules provide system expansion
as Class B operation

 

Capable of supporting two-wire Simplex smoke
detectors and electronic heat detectors plus normally
open contact devices (manual stations, mechanical
heat detectors, etc.)

 

Sounder and Speaker Circuits:

 

Two, four, or six circuit modules provide Class B
system expansion

 

Circuit ratings: 2 A @ 24 VDC; 50 W @ 25 VRMS
(for speaker circuits), or for up to 6 telephones

 

Supervised for opens, grounds, and wire-to-wire
shorts

 

Dual and Triple channel modules have integral
switching relays for selecting the proper audio
channel output

 

Outputs can be programmed for temporal code or
march time code

 

RS-232 Dual Port Communication Module:

 

Up to four additional RS-232 modules total

 

Each port can be vectored by event category

 

Auxiliary Control Relays:

 

Built-in fuse protection per contact

 

Feedback tracks on/off status of remote devices

 

4100-3001, 

four CPU controlled relays, DPDT

contacts rated for 2 A @ 24 VDC

 

4100-3002,

 

four CPU controlled relays, DPDT

contacts rated 10 A @ 24 VDC

 

4100-3003,

 

eight CPU controlled relays, SPDT

contacts rated 3 A @ 24 VDC

 

LED Annunciation:

 

Optional interface modules are available for remote
and/or local control panel annunciation. The LEDs
are programmable for slow rate, fast rate pulse, or
steady illumination.

 

64/64 LED/Switch Controller:

 

Interfaces up to 64 LEDs and 64 switches to the
master controller via serial communications

 

Continuously monitors switches for changes in status

 

Supervises and controls LEDs

 

Supervises LED/switch module placement

 

24 Point I/O Graphic Interface:

 

Each of the 24 points can be individually configured
as either a switch input or a lamp driver output

 

150 mA lamp driver output (+24 VDC common)

 

Outputs can be steady, slow pulse, or fast pulse

 

Switch inputs can monitor two position or three
position switches

 

Lamp test input

 

LED/Switch Modules:

 

Modules contain socketed LEDs to allow
interchanging with different color LEDs to indicate
function

 

Switch modules can be used to perform manual
control such as for HVAC, pressurization fans,
damper control, speaker circuits, etc.

 

MAPNET II

®

, TrueAlarm

®

 Addressable

Module:

 

Connections for up to 120 MAPNET II addressable
devices or TrueAlarm analog sensors per module

 

MAPNET II Line Isolator Modules are available for
protecting Class A addressable circuit loops from
short circuits

 

Remote Unit Interface (RUI) Modules:

 

Provides a supervised serial communication channel
for control and monitoring of remotely located mimic
panels, MINIPLEX transponders, and I/O panels

Simplex Time Recorder Co.

3

S4100-0025 (EN54)  5/99

Summary of Contents for TrueAlarm 4100 Series

Page 1: ...MAL PRESS RESET KEY SYSTEM FAULT POWER SITE SPECIFIC PROGRAMMABLE KEYS LEDS RESET PANEL SILENCE FIRE ALARM REVIEW ALARMS FAULT REVIEW FAULTS SOUNDER FAULT DISABLED DISABLE ENABLE SOUNDERS SOUNDERS SILENCED DISABLEMENT REVIEW DISABLED ZONES SOUNDER SILENCE RESOUND System is Normal 09 36 24 MON 05 APR 1999 4100 FIRE ALARM CONTROL 4100 4120 Series Control and Indicating Equipment shown as a 6 unit pa...

Page 2: ...AULTS FAULT DISABLE ENABLE SOUNDERS SOUNDER FAULT DISABLED SOUNDER SILENCE RESOUND SOUNDERS SILENCED REVIEW DISABLED ZONES DISABLEMENT NEXT PREV System is Normal 09 36 24 MON 05 APR 1999 4 X 40 LCD READOUT LED backlighted during normal conditions and abnormal operating conditions provides up to 40 characters for custom label information EXTENDED FUNCTION KEYPAD accessible with door open select and...

Page 3: ...rammed for temporal code or march time code RS 232 Dual Port Communication Module Up to four additional RS 232 modules total Each port can be vectored by event category Auxiliary Control Relays Built in fuse protection per contact Feedback tracks on off status of remote devices 4100 3001 four CPU controlled relays DPDT contacts rated for 2 A 24 VDC 4100 3002 four CPU controlled relays DPDT contact...

Page 4: ... to 830 Hz in 2 5 seconds recommended for fire alarm and no other purpose High Low Free running signal with a high frequency of 750 Hz for 100 msec and a low frequency of 500 Hz for 400 msec Horn Continuous 500 Hz tone primarily used for coded systems Chime 600 Hz fundamental tone with a 1 5 sec duration used as a free running tone or for coded operation Beep 500 Hz tone of 0 7 sec on 0 7 sec off ...

Page 5: ...des routing and pre amplification of digitized alarm tones and voice messages Actual tones and voice messages are digitally recorded and stored in the audio control board s message memory When called upon an integral Voice Tone Generator VTG recreates the audio waveforms of the prerecorded voice tone messages with completely natural sound The Audio Control board receives instructions from the Mast...

Page 6: ...e 3001 Four Relays 2A with Feedback 15 mA 75 mA 2 Internal 3002 Four Relays 10A with Feedback N A 15 mA 175 mA 4 Internal 3003 Eight Relays 3A with Feedback 2 As Required 25 mA 280 mA 2 Internal Power Supply Options 4100 4120 Description LPC Status Quantity Standby Alarm Module Size 0157 8 A Intelligent Power Supply with Charger 230 VAC 6 Internal 0158 8 A Power Supply 230 VAC 0164 Temperature Com...

Page 7: ...antity Standby Alarm Module Size 4120 6014 Modular Network Interface Board 35 mA 35 mA 2 Internal 4120 0142 Wired Media Card 40 mA 40 mA 4120 0143 Fiber Optic Media Card N A As Required 25 mA 25 mA N A Cabinets and Accessories 4100 4120 Description LPC Status Quantity Standby Alarm Module Size 2052 Four Unit 2053 Six Unit with Glass Door 2062 Four Unit 2063 Six Unit with Solid Door Choose One Per ...

Page 8: ... 4 654 mm 6 3 4 171 mm 26 3 8 670 mm 7 3 4 197 mm 3 3 4 95 mm See chart 3 76 mm 2 1 4 57 mm Installation Detail Side View IMPORTANT Distance between close coupled dual cabinets must be no less than 3 inches 76 mm and no more than 24 inches 610 mm Input Power Requirements Mains Input 230 VAC base models 1 A maximum Mains Input with 230 VAC expansion power supply 2 A maximum Mains Input 4100 0263 10...