Master Controller Module
The 4100/4120-7014 Master Controller Board provides
system control, synchronization, and supervision of all
modules, continuously scanning each module for status
changes. Features include:
•
Operator’s Panel
with LCD and operator keys
•
General Fault Output
•
General Alarm Output,
form “C” contact output
•
RS-232 Dual Port Communications Module,
one port is dedicated to control the user interface
panel, one port is unassigned (can be connected to
remote LCD Annunciator 4604-9202UK)
•
Battery Charger
for up to 110 Ah Batteries
–
Batteries up to 42 Ah may be mounted in the bottom
of the control cabinet
–
Batteries larger than 42 Ah mount external to main
control cabinet
•
Intelligent Power Supply:
–
Two isolated outputs of 4 Amps each at 28.5 VDC
when mains powered (24 VDC nominal during
battery operation)
–
Tap “B” provides 4 A for general purpose sounder
circuits and control power
–
Tap “A” provides 2 A (typical) for sounder circuits
controlling “clean” loads with controlled inrush
current and proper transient suppression (actual
available power depends on total system power
requirements)
Optional Modules Description
•
Conventional Zone Circuits:
–
Eight circuit zone modules provide system expansion
as Class B operation
–
Capable of supporting two-wire Simplex smoke
detectors and electronic heat detectors plus normally
open contact devices (manual stations, mechanical
heat detectors, etc.)
•
Sounder and Speaker Circuits:
–
Two, four, or six circuit modules provide Class B
system expansion
–
Circuit ratings: 2 A @ 24 VDC; 50 W @ 25 VRMS
(for speaker circuits), or for up to 6 telephones
–
Supervised for opens, grounds, and wire-to-wire
shorts
–
Dual and Triple channel modules have integral
switching relays for selecting the proper audio
channel output
–
Outputs can be programmed for temporal code or
march time code
•
RS-232 Dual Port Communication Module:
–
Up to four additional RS-232 modules total
–
Each port can be vectored by event category
•
Auxiliary Control Relays:
–
Built-in fuse protection per contact
–
Feedback tracks on/off status of remote devices
–
4100-3001,
four CPU controlled relays, DPDT
contacts rated for 2 A @ 24 VDC
–
4100-3002,
four CPU controlled relays, DPDT
contacts rated 10 A @ 24 VDC
–
4100-3003,
eight CPU controlled relays, SPDT
contacts rated 3 A @ 24 VDC
•
LED Annunciation:
–
Optional interface modules are available for remote
and/or local control panel annunciation. The LEDs
are programmable for slow rate, fast rate pulse, or
steady illumination.
•
64/64 LED/Switch Controller:
–
Interfaces up to 64 LEDs and 64 switches to the
master controller via serial communications
–
Continuously monitors switches for changes in status
–
Supervises and controls LEDs
–
Supervises LED/switch module placement
•
24 Point I/O Graphic Interface:
–
Each of the 24 points can be individually configured
as either a switch input or a lamp driver output
–
150 mA lamp driver output (+24 VDC common)
–
Outputs can be steady, slow pulse, or fast pulse
–
Switch inputs can monitor two position or three
position switches
–
Lamp test input
•
LED/Switch Modules:
–
Modules contain socketed LEDs to allow
interchanging with different color LEDs to indicate
function
–
Switch modules can be used to perform manual
control such as for HVAC, pressurization fans,
damper control, speaker circuits, etc.
•
MAPNET II
®
, TrueAlarm
®
Addressable
Module:
–
Connections for up to 120 MAPNET II addressable
devices or TrueAlarm analog sensors per module
–
MAPNET II Line Isolator Modules are available for
protecting Class A addressable circuit loops from
short circuits
•
Remote Unit Interface (RUI) Modules:
–
Provides a supervised serial communication channel
for control and monitoring of remotely located mimic
panels, MINIPLEX transponders, and I/O panels