Simplex Time Recorder Co.
6
S4100-0025 (EN54) 5/99
System Type
(select 4100 prefix for stand-alone systems, 4120 prefix for networked systems)
4100/4120-
Description
LPC Status
Quantity
Standby
Alarm
Module Size
8001
Basic Fire Control Panel
8010
Miniplex Control Panel
8201
Control Panel with Audio
8210
Miniplex Control Panel with Audio
8019
Miniplex Transponder
(1)
Choose
One
See below
Master Controller Option
4100/4120-
Description
LPC Status
Quantity
Standby
Alarm
Module Size
4100-7014
Standard
(2)
8” Internal
16” Retainer
4120-7014
EN54 Master
Controller
Assembly with
Display
For 4120 Network
N.A.
Choose
One
625 mA
675 mA
10” Internal
16” Retainer
System Requirements
4100/4120-
Description
LPC Status
Quantity
Standby
Alarm
Module Size
6027
CE Mark Option
6081
Version 8 Software
6051
Non Power-limited
(2)
Required
Not applicable
Conventional Zone Circuits
4100/4120-
Description
LPC Status
Quantity
Standby
Alarm
Module Size
5004
8 Zone Class B
(2)
As Required
75 mA
195 mA
2” Internal
Sounder and Speaker Circuits
4100/4120-
Description
LPC Status
Quantity
Standby
Alarm
Module Size
4001
Two Circuit Class B
16 mA
33 mA
4205
Dual Circuit, Triple Channel Class B
25 mA
80 mA
4321
Six Circuit Class B
(2)
As Required
25 mA
70 mA
2” Internal
Auxiliary Relay Control
4100/4120-
Description
LPC Status
Quantity
Standby
Alarm
Module Size
3001
Four Relays, 2A with Feedback
15 mA
75 mA
2” Internal
3002
Four Relays, 10A with Feedback
N.A.
15 mA
175 mA
4” Internal
3003
Eight Relays, 3A with Feedback
(2)
As Required
25 mA
280 mA
2” Internal
Power Supply Options
4100/4120-
Description
LPC Status
Quantity
Standby
Alarm
Module Size
0157
8 A Intelligent Power Supply with
Charger, 230 VAC
––
––
6” Internal
0158
8 A Power Supply, 230 VAC
––
––
0164
Temperature Compensated Battery
Charger, 230 VAC
(2)
As Required
––
––
4” Internal
Interface Options
4100/4120-
Description
LPC Status
Quantity
Standby
Alarm
Module Size
0110
MAPNET II Addressable Zone Module
470 mA
490 mA
4” Internal
0113
Dual RS232 Module
132 mA
132 mA
0304
Remote Unit Interface (RUI)
(2)
As Required
85 mA
85 mA
2” Internal
Audio Controller Board Options
4100/4120-
Description
LPC Status
Quantity
Standby
Alarm
Module Size
0210
Single Channel Operation
185 mA
185 mA
0211
Dual Channel Operation
220 mA
220 mA
0212
Triple Channel Operation
(3)
Choose One as
Required
220 mA
220 mA
12” Internal
(1)
LPC (Loss Prevention Council) Approval pending for 4100 model series (PIDs) only.
(2)
LPC Approval pending.
(3)
Tested by LPC to verify that no detrimental effect occurred to mandatory EN54 functions.
Module size:
“Internal” = only occupies space behind retainer panel.
“Retainer” = only occupies space at retainer panel level and internal modules can be located behind.
Module Size Reference:
Each unit of space has 16” (406 mm) of panel width available. (8” = 203 mm, 4” = 102 mm, 2” = 51 mm)
Product Selection
(LPC approval status designated per model number, see legend below)