6-2
Points can be selected in one of three ways: through the alarm, fault, or isolate list, using the
MENU keys, or with the ENTRY keypad. Refer to Chapter 5 for information on selecting a
point.
1. Press the FUNCTION key. When you do this, the alphanumeric display shows the first
attribute in the list. (The list is context-sensitive, meaning the list of attributes displayed
for a monitor point differs from the list of attributes displayed for an output point, such as
a relay.)
2. Press the FUNCTION key again. The next option in the list of attributes appears.
Continue to press the FUNCTION key (or use the NEXT and PREV keys) until the option
that you want to display is shown.
3. Press ENTER to see the detailed information for the attribute.
The following table summarizes the attributes available for display via the FUNCTION key.
Category
Attribute
Description
Point address and Zone
number
Displays the point address and zone number of the selected.
Point. If the point’s status is monitored frequently, record this
address for use as a shortcut when subsequently selecting
the point. Refer to Chapter 5 for information on selecting a
point by address.
Card Type and Point type
Displays the point type, which defines the specific function of
the point, and the card type (for example, Class B Multi-
Purpose Monitor Card).
Present Status (Normal,
Alarm, Fault)
The present status of the point – Normal, Alarm, or Fault --
appears on the lower right of the display after you select a
point.
Disconnect/Disable Status
Indicates whether the point has been manually disabled from
the system.
McCulloh Fault (Status of
Class "A" Cards)
Displays whether the Class A card is experiencing a fault
somewhere in the wiring between the card and its devices.
Relay status for Control or
Signal Points
Displays the relay status for a control or signal point. Status
reports as “Relay Status is ON” or “Relay Status is OFF”.
Verification Tallies for
Verification Zones
If the selected point is part of a verification zone, the number
of unverified points in the zone appears.
Coding Status for Coded
Zones
Control Priority for Relays
Allows you to see the control priority for a relay. The control
priority is typically used with Custom Control.
Feedback Point Status
Shows the status – ON or OFF – for a feedback point.
General
Counts for Lists and Virtual
Zones
Indicates the number of points in a list or virtual zone.
Continued on next page
Display-Only Attributes
Step 1. Select a
Point
Step 2. Press the
FUNCTION Key to
See the Attributes
Summary of Display-
Only Attributes
Table 6-1. Display-Only Attributes
firealarmresources.com
Summary of Contents for SafeLINC 4100
Page 2: ...firealarmresources com...
Page 4: ...firealarmresources com...
Page 6: ...firealarmresources com...
Page 8: ...firealarmresources com...
Page 14: ...firealarmresources com...
Page 40: ...firealarmresources com...
Page 50: ...firealarmresources com...
Page 56: ...firealarmresources com...
Page 68: ...firealarmresources com...
Page 82: ...firealarmresources com...
Page 100: ...firealarmresources com...