4-3
Chapter 2 of this manual describes isolating and de-isolating points in alarm. This section
describes isolating and de-isolating non-alarm points. Isolating a non-alarm point does not
prevent it from entering an alarm condition.
There are not separate ISOLATE and DE-ISOLATE keys. Both operations use the ISOLATE
key, but the function of the key depends on the state of the selected point (i.e., if the state of
the point is isolated, pressing the key de-isolates the point. Likewise, if the state of the point
is de-isolated, pressing the key isolates the point).
1. Select the point on which you want to perform the isolate operation. Refer to Chapter 5
for information on selecting points.
2. Press the ISOLATE key.
3. Press the ISOLATE ACK key to confirm the isolate operation.
1. Select the point on which you want to perform the de-isolate operation. Refer to Chapter
5 for information on selecting points
2. Press the ISOLATE key.
3. Press the ISOLATE ACK key to confirm the de-isolate operation.
Do the following when isolating/de-isolating a point within a virtual zone.
1. Select the point within the virtual zone. For example, press the MAP key on the keypad
and then enter the channel and device number. (Use the NET key to insert the hyphen
between the channel and device.)
2. Press the ISOLATE key.
Read the display
to make sure the operation you want to
perform is selected. If necessary, press the ISOLATE key again to toggle the operation of
the ISOLATE key.
3. Press the ISOLATE ACK key to confirm the operation.
Isolating and De-isolating Non-Alarm points
Overview
Isolating a Non-
Alarm Point
De-Isolating a Non-
Alarm Point
Virtual Zones
firealarmresources.com
Summary of Contents for SafeLINC 4100
Page 2: ...firealarmresources com...
Page 4: ...firealarmresources com...
Page 6: ...firealarmresources com...
Page 8: ...firealarmresources com...
Page 14: ...firealarmresources com...
Page 40: ...firealarmresources com...
Page 50: ...firealarmresources com...
Page 56: ...firealarmresources com...
Page 68: ...firealarmresources com...
Page 82: ...firealarmresources com...
Page 100: ...firealarmresources com...