A-8
4100-0110
MAPNET® TRUEALARM™ Addressable Loop
Module
Up to 127 MAPNET Addressable devices or
TrueAlarm Analog Sensors
Up to 10 MAPNET Loop Cards per 4100 system
Supports MAPNET Short Circuit Line Isolator
Modules
4100-0304
Remote Unit Interface Module
Provides a supervised serial communications
channel to remotely located distributed Miniplex®
Transponders and LCD Annunciators
Up to 32 distributed Miniplex® Transponders and/or
LCD Annunciators per 4100 system
4100-3024
24 Relay Input / Output Relay Motherboard
24 CPU controlled relays
Each of the 24 relays can be individually configured
as either an input or an output
SPST contacts rated for 0.5 amps @ 24VDC or
30VAC
4100-0301
64/64 LED / SWITCH Controller
Interfaces up to 64 LEDs and 64 switches to the
master controller for front panel annunciation
4100-0111
Mapnet 2 Quad Isolator Module
The Mapnet Quad isolator provides fault tolerance
and electrical isolation capabilities to 4100 Mapnet
lines. The fault tolerance is twofold: loop open circuit
(Class A operation) and short circuit disconnection
4100-0157A
Provides a 24 VDC, 12 Amp Power Supply with
integral 4 Amp battery charger.
4100-0302
24 Point Graphic Input / Output Module
This card provides up to 24 inputs or outputs to be
programmed and connected into the system. These
24 points can be split up into any combination of inputs
or outputs to suit individual system needs
.
4100-4321
6 Supervised Relay Module
Each card provides 6 circuits of Style Y (class B) signal
circuits All 6 circuit also have two power inputs, one for
every three signal circuits.
Every signal circuit is supervised for ground faults,
opens and line-to-line shorts
4100-0154
VESDA HLI Module
Provides a high level interface to control up to 30
VESDA LaserPlus, Laser Compact , Mini scanners
or E70D units. The module occupies a Mapnet
channel address and requires a VESDA Net
Interface unit to connect to the VESDA units
Continued on next page
4100 Specifications,
Continued
Expansion Modules,
(
continued
)
firealarmresources.com
Summary of Contents for SafeLINC 4100
Page 2: ...firealarmresources com...
Page 4: ...firealarmresources com...
Page 6: ...firealarmresources com...
Page 8: ...firealarmresources com...
Page 14: ...firealarmresources com...
Page 40: ...firealarmresources com...
Page 50: ...firealarmresources com...
Page 56: ...firealarmresources com...
Page 68: ...firealarmresources com...
Page 82: ...firealarmresources com...
Page 100: ...firealarmresources com...