background image

14

2120 Audio System Upgrade, 

Continued

Overview

The migration of the BMUX requires that Flex-35 amplifiers configured as power preamplifier(s) 
in the programmer (amplifier setup screen) be used to replace the power preamplifiers located in 
the adjacent SCC. The Power preamplifiers generate a 25V riser signal that is compatible with 
25V supervision signal, and ignores shorts and opens on these circuits. Trouble supervision of the 
riser is reported by the receiving amplifiers.

In order to insure that the 2120 Audio Riser is capable of generating an earth fault trouble, the riser 
NAC (-) is connected to 0V shield through a 1K resistor (part number 733-973) in class B systems 
for which there is no system 0V reference. See the 

2120 BMUX to 4100U Migration Guide 

(579-824) 

for information regarding riser amplifier wiring on the 4100U that also applies to the 

4100ES.

Class A Risers

In a BMUX system, Class A risers are supervised by a Class A Audio Monitor (assembly 

617-278) mounted to the 2120 riser amplifiers located in the adjoining SCC cabinet. This device 
detects the loss of an audio signal on the class A return lines, and automatically turns on the class 
A relay to drive both sides of the riser in the event of a fault. The Class A audio monitor card uses 
one control and one monitor point on the BMUX local BT. The monitor point is used to detect the 
Class A trouble condition and the control point, and drops 24V power to reset the Class A latch.

The conversion of a BMUX to 4100U/4100ES system will require the power pre-amplifiers 
located in the adjacent SCC to be removed or disabled as part of the upgrade. When Class A audio 
risers are upgraded, refer to Figure 9 for wiring details to connect the riser NAC, the monitor point 
and the control point to the Class A audio monitor board. The monitor and control points will be 
provided by Zone Modules (4100-5005) and Auxiliary Relay Modules (4100-3202, -3204, -3206) 
respectively in the 4100U/4100ES.

Continued on next page

firealarmresources.com

Summary of Contents for 4100-6065

Page 1: ...ents wrapped in anti static material at all times FCC RULES AND REGULATIONS PART 15 This equipment has been tested and found to comply with the limits for a Class A digital device pursuant to Part 15...

Page 2: ...e command When used in style 6 configurations the card includes primary and secondary DC Loop lines so that a single open on any line does not prevent communication to the transponders This publicatio...

Page 3: ...Meaning Coding Color COMM TBL LED 3 Turns on when the Comms Module is not communicating with the system CPU On Steady during comm loss Flashing during firmware failure Yellow Earth LED 1 Earth Fault T...

Page 4: ...ons Table 2 General System Specifications Electrical Specifications Module Input Voltage 24 VDC from FACP Current Consumption 220 mA max with fully loaded channel Wiring Sizes 18 AWG 0 82 mm2 minimum...

Page 5: ...nto the 4100U 4100ES Overview The 4100 6065 BMUX Comms Module mounts on a PDI in a 4100U 4100ES expansion bay It can be mounted on any available double vertical length block Figure 2 BMUX Module Insta...

Page 6: ...y This document also includes cable connection information Install the 4100U 4100ES BMUX Comms Module 1 Refer to Figure 2 to install a PDI board in the second bay use six screws and a Torx T15 screwdr...

Page 7: ...on the job requirements enter an available address from 1 to 119 in the Card Properties dialog before you set the card DIP switch Figure 3 Dialog Box for BMUX Comms Module Properties 5 Verify the car...

Page 8: ...hrough SW1 8 The function of these switches is as follows SW1 1 This switch sets the baud rate for the internal 4100 communications line running between the BMUX Comms Module and the 4100 CPU Set this...

Page 9: ...Procedures Setting the Address Continued Refer to the table below to configure the 4100U 4100ES BMUX Comms Module DIP switched with the proper address Table 3 Switch Settings for Module Addresses Cont...

Page 10: ...y be required in certain installations as determined by the authorized Simplex technical representative TR 9 Download the Slave Exec files BMUX Comms Module software Flex 35 amp software etc CPU Bootl...

Page 11: ...U 4100ES BMUX Comms Module Overview 4100U Shown When configured for Style 6 operation the firmware automatically alternates between the primary and secondary channels T Tapping is permitted for Style...

Page 12: ...ate 1200 or 4800 baud 4 Communications lines must use twisted shielded wiring when run in the same conduit as other circuits DC inductive loads greater than 5A are not permitted in the same conduit 5...

Page 13: ...er supplies Class A Audio Riser Interface Boards Audio user interface LED Switch The 4100U 4100ES replacement of the BMUX audio system will provide the equivalent functionality For further information...

Page 14: ...ss A risers are supervised by a Class A Audio Monitor assembly 617 278 mounted to the 2120 riser amplifiers located in the adjoining SCC cabinet This device detects the loss of an audio signal on the...

Page 15: ...the 2120 Power Preamps must be removed Power to the 2120 Power Preamps must be disconnected 2 Aux power connection on power supply SPS or XPS may be used to provide power to the Class A monitor board...

Page 16: ...arth faults To meet current UL requirements these type of risers will connect the B line of the Riser NAC to the 0V shield line allowing earth faults to be reported by the System Power Supply Figure 1...

Page 17: ...they must be re programmed or removed for compatibility with 4100U 4100ES audio equipment Table 4 Local BT I O points used for audio Local BT I O Point Purpose 4100U 4100ES Equivalent All Talk Switch...

Page 18: ...2120 systems is the same as those used in the 4100U 4100ES With the exception of the End of line resistor no changes are required to the 4100U 4100ES phone card hardware or firmware to support a 2120...

Page 19: ...firealarmresources com...

Page 20: ...579 805 Rev D firealarmresources com...

Reviews: