8
Installation Procedures,
Continued
Setup
Procedures
6. Build the new job (refer to the
4100ES Fire Alarm - Programmer’s Manual
(574-849)
for details
on how to build the new job).
Setting the Address
7. The module address is set via DIP Switch SW1, which is a bank of eight switches. From left to
right (see the figure below) these switches are designated as SW1-1 through SW1-8. The
function of these switches is as follows:
• SW1-1: This switch sets the baud rate for the internal 4100 communications line running
between the BMUX Comms Module and the 4100 CPU.
Set this switch to ON
.
• SW1-2 through SW1-8: These switches set the BMUX Comms Module address within the 4100
FACP. Refer to Table 3 for a complete list of switch settings for all of the possible module
addresses.
Note:
Set these switches to the value assigned to the module by the 4100 Programmer.
Figure 5. DIP Switch SW1
Continued on next page