7
S4007-0002-6 11/2015
Input Power
120 VAC Input 2 A maximum @ 102 to 132 VAC, 50/60 Hz
240 VAC Input 1 A maximum @ 204 to 264 VAC, 50/60 Hz
Battery 6 A maximum @ 24 VDC (during battery operation)
4007ES Power Supply
Output Ratings
Power Supply
Output Rating
4 A output for “Special Application” appliances
Note: The 4 A output rating was determined such that
optional module currents, and external device and appliance
currents can be directly added together, not to exceed 4 A
total.
Output switches to
battery backup
during mains AC
failure or brownout
conditions
IDNAC SLC Ratings
3 A, regulated 29 VDC during Alarm, 127 addresses, 139 unit
loads; DC-DC converter circuit is >92% efficient over
operating range
IDNAC SLC Wiring
Output terminals are rated for 18 to 12 AWG with duplicate
output terminals rated for two wires each, allowing up to four
(4) Class B branch circuit T-taps to be made in the cabinet;
additional T-taps may be made in external wiring junction
cabinets or boxes
Auxiliary Power Tap
2 A maximum, 24 VDC nominal (19.5 to 31.1 VDC)
Compatible Special Application Appliances
Simplex TrueAlert ES and TrueAlert addressable notification appliances; contact
your Simplex product representative for compatible appliances
Battery Charger
Ratings
(sealed lead-acid
batteries)
Battery capacity range
UL and ULC listed for battery charging of 6.2 Ah up to 33 Ah (batteries larger than
18 Ah require a remote battery cabinet)
Charger characteristics
and performance
Temperature compensated, dual rate, recharges depleted batteries within 48 hours
per UL Standard 864; to 70% capacity in 12 hours per ULC Standard S527
Custom Background Display Details
Supported file types: JPG, BMP, GIF, and PNG
Recommended image type is JPG, recommended image size is 480 x 240, and the
file size limit is 100 kb
Environmental
Operating Temperature 32° to 120°F (0° to 49° C)
Operating Humidity Up to 93% RH, non-condensing @ 90° F (32° C) maximum
Additional Technical Reference
Description Document
Description
Document
Installation Manual
579-1102
Single Page Operator Instructions
579-1109
Zone/Relay Module Installation Manual
579-1103
4007ES Hybrid Data Sheet
S4007-0001
Detailed Operator’s Manual
579-1165
Field Installed Optional Modules
Model
Description
Supv.
Alarm
4190-8001*
TrueInsight Remote Service Gateway Module and Programming Selection
Required
Selection
62 mA
73 mA
4190-6106 *
TrueInsight Remote Service Gateway Module Installation Kit
; includes module and
harness; configured for dynamic IP address operation unless ordered with 4190-4016
4190-4016 *
TrueInsight Remote Service Gateway Module for fixed IP Addressing
; optional, select if application will use fixed IP
address
* Refer to data sheet S4100-0063 for additional TrueInsight Service Gateway details
Batteries
Model
Capacity Battery Mounting Details
2081-9272 6.2
Ah
12 V Batteries for cabinet mounting; select one battery model per system standby requirements; order quantity
of two; to be wired in series for 24 VDC
2081-9274 10
Ah
2081-9288 12.7
Ah
2081-9275 18
Ah
2081-9287
25 Ah
For remote mount in Battery Box 4009-9801
Batteries for remote mounting; see battery cabinet details
below
2081-9276
33 Ah
For remote mount in Battery Box 4009-9802
Battery Accessories
Model
Color
Capacity
Dimensions
Description
4009-9801 Beige
For up to 25 Ah
batteries
16 ¼” W x 13 ½” H x 5 ¾” D
(413 mm x 343 mm x 146 mm)
External battery cabinet
without
charger, with locking
solid door and battery harness; for close-nippled
mounting to fire alarm control panel cabinet
4009-9802 Beige
For up to 33 Ah
batteries
25 ¾” W x 20 ¾” H x 4
⅛
” D
(654 mm x 527 mm x 105 mm)
Accessories
Model
Description
2080-9047 DACT cable, 14 ft (4.3 m) long, RJ45 plug one end, spade lugs on the other; order one per phone line connection required
2975-9812 Red semi-flush box trim; 1
7
⁄
16
” (37 mm) wide, four corners and trim pieces for top, bottom, and sides
2975-9813 Platinum semi-flush box trim; 1
7
⁄
16
” (37 mm) wide, four corners and trim pieces for top, bottom, and sides
4081-9018 10
k
Ω
, 1 W end-of-line resistor harness for Class B non-addressable initiating zones (if 4007-9801 is used)
2081-9031
Series resistor for WSO, non-addressable IDCs (N.O. water flow and tamper on same circuit, wires after water flow and before
tamper) 470
Ω
, 1 W, encapsulated, two 18 AWG leads (0.82 mm
2
), 2 ½” L x 1
⅜
” W x 1” H (64 mm x 35 mm x 25 mm)
Module and Accessories Selection Information
(Continued)
General Specifications