S4007-0002-6  11/2015

16" (406 mm)

20-7/8" (530 mm)

20-3/16"

(512 mm)

2

3

4

5

1

6

7

9

21-1/8" (537 mm)

20-7/16"

(519 mm)

4-7/16" Deep (112 mm)

Exposed box for semi-flush mounting

1-3/4" (44 mm) minimum 

Side View Reference

8

10

11

Finished wall surface (including 

semi-flush Trim Kit if used)

3

 

Module Locations: 

1.  Primary location for 4007-9801 Zone/Relay Module, or 4190-6106 TrueInsight Remote Service Gateway. 

2.  Location for a 4007-9802, 25 V Regulator Module (shown), a 4007-9804 IDNAC Dual Class A Isolator, or 

an additional 4007-9801 Zone/Relay Module. 

3.  4007-9803 IDNet+ Loop Expansion Modules, maximum of two (two are shown).  

4.  IDNAC Power Supply Assembly. 

5.  Location for additional 4007-9801 Zone/Relay Module. 

6.  Location for additional 4007-9801 Zone/Relay Module. 

7.  4007-9807 or 4007-9808 City Circuit Module, or 4007-9809 Relay Module. 

8.  Battery location for up to 18 Ah batteries. Note: No conduit entry or wiring in this area, 14-7/8” (378 mm) 

wide. 

9.  4007-9806 SDACT location. 

10.  CPU and User Interface assembly. 

11.  Location for optional 4007-9805 LED Module. 

 

NOTE

:  A system ground must be provided for Earth Detection and transient protection devices. This connection shall be 

made to an approved, dedicated Earth connection per NFPA 70, Article 250, and NFPA 780.

 

 

 4007ES Mounting and Module Location Reference 

Summary of Contents for 4007-9201

Page 1: ...on board memory to allow easy selection of desired revision An internal Ethernet service port and an internal serial service port are available for service computer connections to perform configuratio...

Page 2: ...puter or to the USB drive Module level ground fault searching assists installation and service by locating and isolating modules with grounded wiring WALKTEST silent or audible system test performs an...

Page 3: ...in Menu May 27 2015 12 24 PM System Trouble Screen identifies active troubles with custom labels displayed arrows allow navigation through the list Trouble Log Screen allows review of past troubles wi...

Page 4: ...data sheet S4098 0052 for details TrueAlarm heat sensors can be selected for fixed temperature detection with or without rate of rise detection Utility temperature sensing is also available typically...

Page 5: ...area zone covered by appliances on the notification appliance circuit NAC making it much more difficult and costly to locate and correct the source of a problem Using the TrueAlert magnet test allows...

Page 6: ...num Models with BA are available assembled in the USA by adding the suffix BA 6 S4007 0002 6 11 2015 Factory Programming Options Model Description 4007 8810 Factory Programming select 4007 0831 Custom...

Page 7: ...tion Manual 579 1103 4007ES Hybrid Data Sheet S4007 0001 Detailed Operator s Manual 579 1165 Field Installed Optional Modules Model Description Supv Alarm 4190 8001 TrueInsight Remote Service Gateway...

Page 8: ...9803 IDNet Loop Expansion Modules maximum of two two are shown 4 IDNAC Power Supply Assembly 5 Location for additional 4007 9801 Zone Relay Module 6 Location for additional 4007 9801 Zone Relay Module...

Page 9: ...009 IDNet NAC Extender S4009 0002 Battery and Battery Cabinet Reference S2081 0006 4003EC Voice Control Panel S4003 0002 Seismic Battery Brackets Reference S2081 0019 4606 Series Color LCD Touchscreen...

Page 10: ...f Test TrueAlert addressable appliance not TrueAlert ES addressable appliance Note Additional TrueAlert ES Self Test information is detailed in Operating Instructions 579 1165 shipped with the panel S...

Reviews: