2
Each manual station has a unique address, which is set using a series of dip
switches located inside the manual station. The manual station’s address must
match the address listed in the specification sheets of the 2120 Job
Configuration Report or the Programmer’s Report for the 4020, 4100+, or 4120
system.
1. Set the manual station’s address using Table 2. See Figure 1 for the
location of the switches. Use a small screwdriver or pen to set the switches.
When positioning each dip switch, note that 0 equals ON and 1 equals OFF.
Note:
The address you set must match the address entered in the 2120 Job
Configuration Report.
2. Mark an address label with the appropriate address for the manual station.
Shade a box for each dip switch in the ON position. Leave the OFF
positions blank. Apply the label to the manual station near the dip switches.
3. Double-check the address before wiring the manual station.
1. Set the manual station’s address using Table 2. See Figure 1 for the
location of the switches. Use a small screwdriver or pen to set the switches.
When positioning each dip switch, note that 0 equals ON and 1 equals OFF.
Note:
The address you set must match the address entered in the
Programmer’s Report for the 4020, 4100+, or 4120 system.
2. Mark an address label with the appropriate address for the manual station.
Shade a box for each dip switch in the ON position. Leave the OFF
positions blank. Apply the label to the manual station near the dip switches.
3. Double-check the address before wiring the manual station.
Figure 1. Location of Dip Switches
Continued on next page
Setting the Manual Station’s Address
Introduction
Address Setting for the 2120
CDT System (MAPNET)
Address Setting for the 4020,
4100+, or 4120 System
(MAPNET Only)
Technical Manuals Online! - http://www.tech-man.com