Use Table 2 to convert a decimal address, such as address 7, to its binary 
equivalent.  This binary number can then be set on the manual station as shown 
in the figure at the top of the table. 
 
 

Table 2.  Address Settings 

 

0000 1000 0100 1100 0010 1010 0110 1110

0000

0

16

32

48

64

80

96

112

1000

1

17

33

49

65

81

97

113

0100

2

18

34

50

66

82

98

114

1100

3

19

35

51

67

83

99

115

0010

4

20

36

52

68

84

100

116

1010

5

21

37

53

69

85

101

117

0110

6

22

38

54

70

86

102

118

1110

7

23

39

55

71

87

103

119

0001

8

24

40

56

72

88

104

120

1001

9

25

41

57

73

89

105

121

0101

10

26

42

58

74

90

106

122

1101

11

27

43

59

75

91

107

123

0011

12

28

44

60

76

92

108

124

1011

13

29

45

61

77

93

109

125

0111

14

30

46

62

78

94

110

126

15

31

47

63

79

95

111

127

LSB

MSB

1

2

3

4

5

6

7

8

1111

DIP SWITCHES 5 THRU 8

RESERVED FOR

FUTURE USE

DIP

SWITCHES

1 THRU 4

ON

OFF

1 = ON

0 = OFF

DIPSWITCH IS SHOWN SET AT ADDRESS 7.

 

 

 

 
 
 
 
 

Setting the Manual Station’s Address, 

Continued

 

Address and Dip Switch 
Conversion Chart 

Technical Manuals Online! - http://www.tech-man.com

firealarmresources.com

Summary of Contents for 2099-9135

Page 1: ...ect to either a 2120 Multiplex Communicating Device Transponder CDT 4020 4100 or 4120 system by a twisted shielded recommended wire pair MAPNET and receive both power and data over this wire pair Inst...

Page 2: ...e manual station near the dip switches 3 Double check the address before wiring the manual station 1 Set the manual station s address using Table 2 See Figure 1 for the location of the switches Use a...

Page 3: ...85 101 117 0110 6 22 38 54 70 86 102 118 1110 7 23 39 55 71 87 103 119 0001 8 24 40 56 72 88 104 120 1001 9 25 41 57 73 89 105 121 0101 10 26 42 58 74 90 106 122 1101 11 27 43 59 75 91 107 123 0011 12...

Page 4: ...0 CDT 4020 4100 or 4120 panel cabinet drawing for MAPNET to panel connections Recommended MAPNETfi FROM 4020 4100 4120 OR CDT PANEL MAPNETfi TO OTHER ADDRESSABLE DEVICES A A A 1 2 3 4 A SHIELD Figure...

Page 5: ...ired or a receptacle box such as a Wiremold No 57441S DEEP or equivalent with surface trim Flush Installation Use two 3 x 2 x2 gangable switch boxes ganged together with flush trim Install the manual...

Page 6: ...pane fits Callout D in Figure 4 identifies the location of this tab 3 Fit the bottom of the glass pane into the notch located in the glass retainer See E in Figure 4 4 Push the glass retainer A into p...

Page 7: ...open the station 2 Carefully clean any pieces of broken glass from the unit 3 Position the rod in the slot located near the bottom of the station See Figure 5 for the location of the slot Close the st...

Page 8: ...574 155 Rev A White Text Technical Manuals Online http www tech man com firealarmresources com...

Reviews: