Addressable Manual Stations
2099-9135, -9761, -9795, -9796, & -9797
Installation Instructions
2000 Simplex Time Recorder Co., Westminster, MA 01441-0001 USA
All specifications and other information shown were current as of publication, and are subject to change without notice.
574-155
Rev. A
These instructions describe installing and setting the address for a manual
station (single action, double action, or local). Installing a manual station
consists of the following tasks:
•
Setting the Address.
The address, which uniquely identifies the manual
station on the MAPNET II
channel, must be set in two places
the dip
switch on the rear of the manual station and through the programmer. The
address must match in both places.
•
Wiring.
Addressable manual stations connect to either a 2120 Multiplex
Communicating Device Transponder (CDT), 4020, 4100+, or 4120 system
by a twisted, shielded (recommended) wire pair (MAPNET), and receive
both power and data over this wire pair.
•
Installing.
Manual stations mount to a variety of standard switch and back
boxes.
•
Maintaining.
Depending on the model of manual station, you may also
need to replace a small pane of glass or a glass rod following activation.
Table 1 summarizes the features of each manual station model.
PID
Single
Action
Glass
Double
Action
Push
Double
Action
MAPNET
I
MAPNET
II
Local
Cover
No
Simplex
Logo
2099-9135
X
X
X
2099-9761
X
X
2099-9795
X
X
2099-9796
X
X
2099-9797
X
X X
This publication discusses the following topics:
Topic
See Page #
Setting the Manual Station’s Address
2
Wiring 4
Installing the Manual Station
5
Replacing Glass Pane/Glass Rod
6
Overview
Features
In this Publication
Technical Manuals Online! - http://www.tech-man.com
firealarmresources.com