User manual for Digital Indicator and cooperating software
Register Write
Range
Register description
1Fh
Yes
0÷3
Control registry for time-related settings:
0
- startup of continued update of registries 18h ÷ 1Eh by internal
clock (current time and date),
80h
- stopping update of registries 18h ÷ 1Eh by internal clock
(automatically after writing one of 18h ÷ 1Eh registries). In this status
18h ÷ 1Eh registries can be written with new values in order to update
internal clock settings. Updating the clock settings with contents of
18h ÷ 1Eh registries can be executed by sending the following
commands to the control registry:
1
- hour update on the basis of (1Ch ÷ 1Eh) registries’ contents;
2
- date update on the basis of (18h ÷ 1Bh) registries’ contents;
3
- time and date update on the basis of (18h ÷ 1Eh) registries’
contents.
After sending commands
1
,
2
or
3
the contents of registries
automatically return to 0.
20h
2
Yes
0÷199
Address of device
21h
No
Device identification code
22h
3
Yes
0÷7
“
Baud rate
” parameter in “
RS485 port settings
” menu (baud rate):
0
- 1200;
1
- 2400;
2
- 4800;
3
- 9600;
4
- 19200;
5
- 38400;
6
- 57600;
7
- 115200;
23h
4
Yes
0÷1
“
Conf. change
” parameter in “
RS485 port settings
” menu
(permission to write registers):
0
- write denied;
1
- write allowed.
28h
No
Firmware version
29h
No
Compilation number
2Ah
No
Higher (2
nd
) word of serial number
2Bh
No
Lower (1
st
) word of serial number
2Ch
No
1, 4, 8
Number of units’ measurement channels
Configuration parameters for channel No. 1
40h
Yes
0÷2
“
Input type
” parameter in “
Inputs settings
” submenu for channel 1:
0
- inactive;
1
- 0-20mA;
2
- 4-20mA
41h
Yes
-9999÷9999 “
Lo value
” parameter in “
Inputs settings
” submenu for channel 1
(not considering decimal point)
42h
Yes
-9999÷9999 “
Hi value
” parameter in “
Inputs settings
” submenu for channel 1 (not
considering decimal point)
43h
Yes
0÷3
“
Dec. point
” parameter in “
Inputs settings
” submenu for
channel1:
0
- 0;
1
- 0,0;
2
- 0,00;
3
- 0,000
44h
Yes
0÷5
“
Filter
” parameter in “
Inputs settings
” submenu for channel 1:
(filtration coefficient)
45h
Yes
0÷399
“
Lower ext.
” parameter in “
Inputs settings
” submenu for channel 1
expressed in 0.01 mA (not considering decimal point)
46h
Yes
0÷199
“
Upper ext.
” parameter in “
Inputs settings
” submenu for channel 1
expressed in 0.01 mA (not considering decimal point)
36