User manual - METER SWE-94-U
“dELP”
- this option allows user to delete any of the points of the user defined characteristic.
After selection current number of points of the user defined characteristic is
displayed for about approx. 1.5 sec. After that device waits for selection of point
being deleted (by
[^]
,
[v]
buttons). The short pressing of
[ENTER]
button causes by
switching between
X
and
Y
value of the displayed point. The long press (press and
hold at least 2 sec) of
[ENTER]
button causes by displaying
„dEL?”
ask. If
[ENTER]
button is pressed again, current point is deleted and new updated number
of points of the user defined characteristic is displayed.
“EdtP”
- this option allows user to modify of particular point of the user defined
characteristic. After selection current number of points of the user defined
characteristic is displayed for about approx. 1.5 sec. After that device waits for
selection of point being edited (by
[^]
,
[v]
buttons). The short pressing of
[ENTER]
button causes by switching between
X
and
Y
value of the displayed point. The long
press (press and hold at least 2 sec) of
[ENTER]
button causes by entering to edit
the selected coordinate of the point. Modification of the coordinates is done
accordingly to numerical parameters edition.
“AddP”
,
”dELP”
and
“EdtP”
options are available only if the user defined
characteristic is used (it means when parameter
“CHAr”
=
”USEr”
).
“Lo r”
,
”Hi r”
- these parameters define the expansion of nominal range in percent. They
determine the permissible range of input signal (Figure 7.1).
The permissible range allow user to exceed the
nominal range
of input signal.
If input value is contained in the permissible range a proper result is displayed.
If input signal exceeds this range (defined by
“Lo r”
and
“Hi r”
),
“-Lo-”
or
“-
Hi-”
warning
is displayed
depend on input signal value.
Figure 7.1 E
xample of definition of permissible range of input signal -
“
Lo r
” and “
Hi r
” parameters (
“4-20”
mode)
The
“Lo r”
parameter is important if input is set to
“4-20”
,
“1-5”
or
“2-10”
mode
only, and determines lower border of the permissible range. In the other cases (for
current and voltage ranges), lower border of the permissible range is always 0.
For example if input is set to
“4-20”
mode, then lower border is calculated due to
expression:
I
min
= 4 mA - 4 mA ×
“Lo r”
%.
21
”
Lo r
” = 75,0% (3 mA)
”
Hi r
” = 5,0 % (1 mA)
4
21
permissible measurement range
measurement result is displayed
regardless on nominal range exceeding
nominal measurement range (4-20mA)
[mA]
20
22
1
0
I
min
I
max
display
message ”
-Lo-
”
display
message ”
-Hi-
”
i