User manual - METER SWE-94-U
7.3.3.
“inPt” menu (parameters of current and voltage inputs)
”CHAr”
- this option presets type of the conversion characteristic, and can be set to:
”Lin”
- linear
“Sqr”
- square
“Sqrt”
- square root
When one of those characteristics is chosen display
range is defined by
“Lo C”
and
“Hi C”
.
“USEr”
- user defined characteristic. Maximal length 20 points. Every point is
defined by user. Adding, Editing and Deleting of points is done by options
„
AddP
”, „
EdtP
”, „
dELP
” („
InPt
” menu) respectively.
If user defined characteristic is selected, and if number of defined points is lower
than 2 then warning ”
Errc
” is displayed in measurement mode.
The process of displayed result calculation is described in details in
DISPLAY VALUES
CALCULATION
paragraph.
”Pnt”
- decimal point position. It can be set to one of:
“ 0”
,
“ 0.0”
,
“ 0.00”
,
“0.000”
Decimal point position is changed by
[^]
,
[v]
buttons.
“Lo C”
“Hi C”
These parameters describe the values displayed for minimum and maximum input
current. For example, if input type is set to 4-20 mA
“Lo C”
parameter defines the
value displayed when input current is equal 4 mA, and
“Hi C”
parameter defines
the value displayed for 20 mA of input current. Available range for these
parameters: -999 ÷ 9999. Negative values can be set by entering
'-'
sign on the first
position (by use of
[^]
,
[v]
buttons).
If user defined characteristic is selected
(parameter
“CHAr”
=
”USEr”
) the
parameters „
Lo C
” and „
Hi C
” are not available for modification, due to their values
are calculated from defined characteristic.
“AddP”
- this menu allow user to add single point to the user defined characteristic.
After selection of this option device waits for „
X
” and „
Y
” coordinates of new point.
Modification of the coordinates is done accordingly to numerical parameters edition.
Coordinate „
X
” defines the percentage ratio of input current to selected current
range. The „
X
” range: -99,9 ÷ 199,9. Coordinate „
Y
” defines displayed value for
particular „
X
” value. The „
Y
” value can be changed in range: -999 ÷ 9999, decimal
point position depend on
„Pnt”
parameter (menu
”inPt ”
).
•
User can not enter two points with the same value of „
X
” coordinate. If user trays
to do it,
”Err”
warning is displayed. To modify any defined point use
”EdtP”
option.
•
To distinguish „
X
” and „
Y
” coordinates, if „
X
” coordinate is displayed an
additional decimal point on utmost right position is displayed.
•
If user defined characteristic is selected, and if number of defined points is lower
than 2 then warning ”
Errc
” is displayed in measurement mode.
20
i
i
i
Summary of Contents for SWE-94-U
Page 38: ...User manual METER SWE 94 U 38...
Page 39: ...User manual METER SWE 94 U 39...