User manual - METER SWE-94-U
Register
Write
Range
Register description
16h
Yes
0 ÷ 999
“
Lo r
” parameter in “
InPt
” menu, in 0.1%
17h
Yes
0 ÷ 199
“
Hi r
” parameter in “
InPt
” menu, in 0.1%
18h
Yes
-99 ÷ 99
“
toFS
” parameter in “
InPt
” menu (shift of measurement scale),
expressed by 0.1°C (for RTD input) or by 1.0°C (for TC input)
19h
Yes
1 ÷ 2
“
Conn
” parameter in “
InPt
” menu (RTD input connection method):
1
- “
3 in
”;
2
- “
2 in
”
20h
1
Yes
0 ÷ 199
Device address
21h
No
Device identification code (ID)
22h
2
Yes
0 ÷ 7
“bAud”
parameter in
“rS”
menu (baud rate);
0
- 1200 baud;
1
- 2400 baud;
2
- 4800 baud;
3
- 9600 baud;
4
- 19200 baud;
5
- 38400 baud;
6
- 57600 baud;
7
- 115200 baud
23h
3
Yes
0 ÷ 1
“mbAc”
parameter in
“rS”
menu (permission to write registers via
RS-485 interface);
0
- write denied ;
1
- write allowed
25h
Yes
0 ÷ 5
“rESP”
parameter in
“rS”
menu (additional response delay);
0
- no additional delay;
1
- ”
10c
” option;
2
- ”
20c
” option;
3
- ”
50c
” option;
4
- ”
100c
” option;
5
- ”
200c
” option;
27h
Yes
0 ÷ 99
“mbtO”
parameter in
“rS”
menu (maximum delay between
received frames);
0
- no delay checking;
1
÷
99
- maximum delay expressed in seconds
2Dh
Yes
1 ÷ 8
“
bri
” parameter (display brightness);
1
- the lowest brightness;
8
- the highest brightness
2Fh
Yes
0 ÷ 1
“
Edit
” parameter (numerical parameters edit mode);
0
- „
dig
” mode;
1
- „
SLid
” mode
50h
Yes
0 ÷ 1
“
modE
” parameter in “
HOLd
” menu (type of detected changes):
0
- peaks;
1
- drops
51h
Yes
0 ÷ 9999
“
PEA
” parameter in “
HOLd
” menu (minimum detectable change, no
decimal point included)
52h
Yes
0 ÷ 199
“
timE
” parameter in “
HOLd
” menu,
maximum peaks' (or drops')
display time expressed in seconds
53h
Yes
0 ÷ 1
“
HdiS
” parameter in “
HOLd
” menu:
0
- “
rEAL
” mode ;
1
- “
HOLd
” mode
70h
4
Yes
-999 ÷ 1999
The value of „
X
” coordinate of point
no. 1
of the user defined
characteristic, expressed in 0.1%
71h
4
Yes
-999 ÷ 9999
The value of „
Y
” coordinate of point
no. 1
of the user defined
characteristic, no decimal point included
72h
5
÷ 95h
5
Further pairs of „
X
” - „
Y
” coordinates of points
no. 2
÷
19
of the user
defined characteristic
96h
4
Yes
-999 ÷ 1999
The value of „
X
” coordinate of point
no. 20
of the user defined
characteristic, expressed in 0.1%
97h
4
Yes
-999 ÷ 9999
The value of „
Y
” coordinate of point
no. 20
of the user defined
characteristic, no decimal point included
33