User manual - METER SRP-N1186
Register Write
Range
Register description
11h
Yes
0 ÷ 5
“
CHAr
” parameter in “
InPt
” menu (characteristic type)
0
- linear ;
1
- square;
2
- square root;
3
- user defined;
4
- volume
characteristics of a cylindrical tank in the vertical position;
5
-
volume characteristics of a cylindrical tank in the horizontal position
12h
Yes
0 ÷ 5
“
FiLt
” parameter in “
InPt
” menu (measurement filtering rate)
13h
Yes
0 ÷ 3
“
Pnt
”parameter in “
InPt
” menu (the copy of 04h register, decimal
point position)
0
- “
0
”;
1
- “
0.0
”;
2
- “
0.00
”;
3
- “
0.000
”
14h
Yes
see descr.
“
Lo C
” parameter in “
InPt
” menu, no decimal point included – higher
word
15h
Yes
see descr.
“
Lo C
” parameter in “
InPt
” menu, no decimal point included – lower
word
16h
Yes
see descr.
“
Hi C
” parameter in “
InPt
” menu, no decimal point included – higher
word
17h
Yes
see descr.
“
Hi C
” parameter in “
InPt
” menu, no decimal point included – lower
word
18h
Yes
see descr.
“
Lo r
” parameter in “
InPt
” menu, in 0.001% – higher word
19h
Yes
see descr.
“
Lo r
” parameter in “
InPt
” menu, in 0.001% – lower word
1Ah
Yes
see descr.
“
Hi r
” parameter in “
InPt
” menu, in 0.001% – higher word
1Bh
Yes
see descr.
“
Hi r
” parameter in “
InPt
” menu, in 0.001% – lower word
20h
2
Yes
0 ÷ 199
Device address
21h
No
Device identification code (ID)
22h
3
Yes
0 ÷ 7
“bAud”
parameter in
“rS”
menu (baud rate);
0
- 1200 baud;
1
- 2400 baud;
2
- 4800 baud;
3
- 9600 baud;
4
- 19200 baud;
5
- 38400 baud;
6
- 57600 baud;
7
- 115200 baud
23h
4
Yes
0 ÷ 1
“mbAc”
parameter in
“rS”
menu (permission to write registers via
RS-485 interface);
0
- write denied ;
1
- write allowed
24h
Yes
see descr.
Parameters of “
SECU
” menu (binary format (0 - „
oFF
”, 1 - „
on
”):
bit 0
- “
A r1
” parameter;
bit 1
- “
A r2
” parameter
25h
Yes
0 ÷ 5
“rESP”
parameter in
“rS”
menu (additional response delay);
0
- no additional delay;
1
- ”
10c
” option;
2
- ”
20c
” option;
3
- ”
50c
” option;
4
- ”
100c
” option;
5
- ”
200c
” option;
27h
Yes
0 ÷ 99
“mbtO”
parameter in
“rS”
menu (maximum delay between
received frames);
0
- no delay checking;
1
÷
99
- maximum delay expressed in seconds
28h
Yes
see descr.
“
t h1
” parameter in “
InPt
” menu, no decimal point included – higher
word
29h
Yes
see descr.
“
t h1
” parameter in “
InPt
” menu, no decimal point included – lower
word
2Ah
Yes
see descr.
“
t h2
” parameter in “
InPt
” menu, no decimal point included – higher
word
53