WARNINGS
– The smoke flue and the connection to the flue pipe
must be in compliance with the national and local
Standards and Legislation in force.
– The use of rigid ducts which are resistant to
temperature, condensate, mechanical stress and
are air-tight is compulsory.
– Outlet ducts which are not isolated are a risk of
danger.
2.11.1 Coaxial duct (Ø 60/100mm and Ø 80/125mm)
Coaxial accessories
Description
Code
Ø 60/100
mm
Ø 80/125
mm
Coaxial duct kit
8084811
8084830
Extension W. 1000 mm
8096103
8096130
Extension W. 500 mm
8096102
-
Vertical extension W. 200 mm with
smoke analysis take-off point
8086908
-
Adapter for Ø 80/125 mm
-
8093120
Additional 90° curve
8095801
8095820
Additional 45° curve
8095900
8095920
Tile with joint
8091300
8091300
Roof outlet terminal W. 1284 mm
8091200
8091200
Vertical condensation recovery W. 200
mm
8092803
8092803
Load loss - Equivalent lengths
Model
Leq (linear metres)
Ø 60/100
mm
Ø 80/125
mm
90° curve
1
1
45° curve
0,5
0,8
Minimum-Maximum Lengths
Model
Duct Length Ø 60/100
Duct Length Ø 80/125
W
Horizontal
(m)
H Vertical
(m)
W
Horizontal
(m)
H Vertical
(m)
Min. Max. Min. Max. Min. Max. Min. Max.
Brava Slim
25 BF
-
3,5
1,3
(*)
5
3,5
6
4
7
Brava Slim
30 BF
-
3,0
1,3
(*)
5
3
6
4
7
m
CAUTION
(*) Vertical condensate recovery MUST be introduced
for vertical ducts (Type C32) or vertical sections of the
duct (Type C42) longer than 1.3m.
Diaphragms for coaxial ducts
Boilers leave the factory equipped with a diaphragm (1) with the
following characteristics:
– Brava Slim 25 BF: diaphragm Ø 79 mm
– Brava Slim 30 BF: diaphragm Ø 81 mm.
1
Fig. 14
When the outlets are Type C12 or C42 the diaphragm is to be
removed or kept following the indications below:
Model
Gas diaphragm
for duct L
Brava Slim 25 BF
YES
(leave mounted)
< 1 m
Brava Slim 30 BF
Brava Slim 25 BF
NO
(remove it)
> 1 m
Brava Slim 30 BF
When the outlet isType C32 (vertically straight without any
curves), the presence of the diaphragm modifies the maximum
length of the duct as shown below:
Model
Gas diaphragm
Max L (m)
Brava Slim 25 BF
YES
2,5
Brava Slim 25 BF
NO
5
Brava Slim 30 BF
YES
2,5
Brava Slim 30 BF
NO
5
2.11.2 Separate ducts (Ø 80mm)
Constructing outlets for separate ducts indicates the use of the
"air-smoke split pipe system". This is to be ordered separately
from the boiler and when connected to the other accessories,
from those listed in the table below, completes the smoke-
outlet/ combustion air inlet assembly.
The total maximum length obtained from the length of the outlet
and inlet pipes is determined by the load loss of the individual
accessories and must not be greater than 9 mm H
2
O for Brava
Slim 25 BF
and 9.5 mm H
2
O Brava Slim 30 BF.
Separate accessories
Description
Code
Diameter Ø 80 (mm)
Air-smoke split pipe system (with take-
off point) + Diaphragm
8093020
90° curve M-F (6 pieces)
8077410
90° curve M-F (with take-off point)
8077407
90° curve M-F (insulated)
8077408
Extension W. 1000 mm (6 pieces)
8077309
Extension W. 1000 mm (insulated)
8077306
Extension W. 500 mm (6 pieces)
8077308
Extension W. 135 mm (with take-off
point)
8077304
Wall outlet terminal
8089501
Internal and external ring nut kit
8091500
Inlet terminal
8089500
45° curve M-F (6 pieces)
8077411
Condensate recovery W. 135 mm
8092800
Collector
8091400
Tile with joint
8091300
Roof outlet terminal W. 1390 mm
8091201
Condensate recovery Tee
8093300
Inlet/outlet fitting Ø 80/125 mm
8091401