70
EN
1.5
Technical features
DESCRIPTION
Brava Slim 25 BF
Brava Slim 30 BF
CERTIFICATIONS
Country of intended installation
IT – ES – PT – GR – SI
Fuel
G20 - G30/G31
PIN number
1312CP5935
Category
II2H3+
Type
B22P - B32P - B52P
C12 - C12X - C32 - C32X - C42 - C42X - C52 - C52X - C62 - C62X - C82 - C82X
NO
x
class
3 (< 150 mg/kWh)
HEATING PERFORMANCE
HEAT INPUT
Nominal
kW
25,5
30,0
Minimum
kW
9,2
10,8
HEAT OUTPUT
Nominal (80-60°C)
kW
23,7
28,1
Minimum (80-60°C)
kW
7,8
9,2
EFFICIENCY
Max useful efficiency (80-60°C)
%
93,0
93,7
Min useful efficiency (80-60°C)
%
84,8
85,2
Useful efficiency at 30% of load (50-30°C)
%
90,5
91,1
Thermal efficiency (EEC 92/42)
Losses after shutdown at 50°C
W
71
75
DOMESTIC HOT WATER PERFORMANCE
Rated heat input
kW
25,5
30,0
Minimum heat input
kW
9,2
10,8
D.H.W. flow rate Δt 30°C
l/min
11,3
13,4
Continuous D.H.W. flow rate (Δt 25°C / Δt 35°C)
l/min
13,6 / 9,7
16,1 / 11,5
Minimum D.H.W. flow rate
l/min
2,2
2,2
Max / Min Pressure
bar
7 / 0,4
7 / 0,4
kpa
700 / 40
700 / 40
ELECTRICAL SPECIFICATIONS
Power supply voltage
V
230
Frequency
Hz
50
Electric power consumption
W
112
113
Electric degree of protection
IP
X5D
COMBUSTION DATA
Smoke temperature at Max/Min flow (80-60°C)
°C
142,5 / 96,4
151,9 / 100,8
Maximum smoke flow Min/Max
g/s
17 / 16
19 /19
CO
2
at Max/Min (G20) flow rate with separate chimneys
%
6,7 / 2,1
7,1 / 2,3
CO
2
at Max/Min (G31) flow rate with separate chimneys
%
7,7 /2,6
7,8 /2,7
NOZZLES - GAS
Number of nozzles
n°
11
13
Nozzle diameter (G20)
mm
1,30
1,30
Nozzle diameter (G30/G31)
mm
0,80
0,78
Gas consumption at Max/Min flow rate (G20)
m
3
/h
2,70 / 0,97
3,17 / 1,14
Gas consumption at Max/Min flow rate (G30)
Kg/h
2,01 / 0,72
2,36 / 0,85
Gas consumption at Max/Min flow rate (G31)
Kg/h
1,98 / 0,71
2,33 / 0,84
Gas supply pressure (G20/G30/G31)
mbar
20 / 28-30 / 37
kpa
2 / 2,8-3 / 3,7
TEMPERATURE - PRESSURE
Max operating temperature
°C
85
85
Heating adjustment range
°C
21 ÷ 80
21 ÷ 80
Domestic hot water adjustment range
°C
10 - 60
10 - 60
Max operating pressure
bar
3
kpa
300
Water content in boiler
l
3,05
3,65
Lower Heat Output (Hi)
G20 Hi.
9.45 kW/m
3
(15°C, 1013 mbar) - G30 Hi. 12.68 kW/kg (15°C, 1013 mbar) - G31 Hi. 12.87 kW/kg (15°C, 1013 mbar)
Summary of Contents for Brava Slim BF
Page 33: ...33 ES ...
Page 65: ...65 PT ...
Page 97: ...97 EN ...
Page 129: ...129 RU ...
Page 130: ...130 ...
Page 131: ...131 ...