91
EN
Type
No. Fault
Solution
ALL
81 Block due combustion
during start-up
- Check for blockage in
chimney
- Check air diaphragm (for
BF models)
- Check gas calibration
- Bleed the air from the gas
circuit
ALL
82
Block due to numerous
combustion control
failures
- Check electrode
- Check outlets
- Check air diaphragm (for
BF models)
- Check gas calibration
ALL
83 Irregular combustion
(temporary error)
- Check for blockage in
chimney
- Check air diaphragm (for
BF models)
- Check gas calibration
ALL
84
Flow rate reduced
for (presumed) low
pressure on mains gas
- Check gas flow rate
ALL
88 Internal error (board
component protection)
- Check the board is working
- Replace board
ALL
89 Unstable combustion
feedback signal error
- Check electrode
- Check outlets
- Check air diaphragm (for
BF models)
- Check gas calibration
ALL
90 Combustion set cannot
be reached error
- Check electrode
- Check outlets
- Check air diaphragm (for
BF models)
- Check gas calibration
ALL
92
System has reached
maximum air
correction error (at the
minimum flow rate)
- Check electrode
- Check outlets
- Check air diaphragm (for
BF models)
- Check gas calibration
ALL
93 Combustion set cannot
be reached error
- Check electrode
- Check outlets
- Check air diaphragm (for
BF models)
- Check gas calibration
Type
No. Fault
Solution
ALL
95 Flame signal micro
interruptions error
- Check electrode
- Check board
- Check electric power supply
- Check gas calibration
ALL
96 Block due to clogging
in smoke outlet
- Check for blockage in
chimney
- Check the smoke outlet
and electrode position (not
touching the burner)
ALL
98 SW error, board start-
up
- Contact the Technical
Assistance Centre
ALL
99 General board error
- Contact the Technical
Assistance Centre
-
-
Frequent relief valve
intervention
- Check circuit pressure
- Check expansion vessel
-
-
Limited production of
domestic hot water
- Check the diverter valve
- Check that plate heat
exchanger is clean
- Check domestic hot water
circuit valve
4.6.1
Maintenance request
When it is time to perform maintenance on the boiler, the
c
symbol shows on the display.
Contact the technical assistance service to organise the
necessary work.
4.7
Troubleshooting for the pump with LED (if present)
LED colour
Pump status
Fault
Possible solution
Red-Green
flashing
"Transient safety shutdown"; Anomaly
in progress
After eliminating the anomaly, the pump
restarts automatically
Network voltage too high or too low;
(160V > Vn > 280V)
- Check network voltage
Motor overload; rotor friction or blockage
due to the presence of debris
- Check the characteristics of the system
water; clean the system of any debris
Excessive speed; the pump rotor is
actuated by an external factor and is
rotating at a speed exceeding the maximum
permitted speed
- Check that there is no external flow in the
system (no other pump in operation)
Overcurrent; stator winding is in short
circuit due to water
- Check for leaks in the system
The temperature inside the motor is too
high
- Check the water temperature in relation
to ambient temperature
The pump is obstructed by an external flow
(> 1200l/h) in the opposite direction
- Eliminate or reduce the external flow (<
1200l/h)
Flashing red
"Permanent safety shutdown"
Pump blocked due to debris in the system
- Remove and reconnect the electrical
power supply (OFF - ON)
Fault in the electronic board and/or the
motor
- If the "red LED" continues to flash:
- REPLACE THE PUMP
LED off
Stationary
No electrical power
- Check the electrical power connection
LED faulty
- Check if the pump can operate
Electronic board faulty
- REPLACE THE PUMP