90
EN
4.5
Unscheduled maintenance
If replacing the
electronic board
, the user MUST set the
parameters as indicated in the table.
Type No. Description
Setting for
Brava
Slim HE ErP
24 25 30 35 40
PAR 01 Index showing boiler power in kW
0=24; 1 = 25; 2 = 30; 3 = 35; 4 = 40
0
1
2
3
4
PAR 02
Hydraulic configuration
0 = rapid
1 = storage tank with thermostat or
heating only
2 = hot water tank with sensor
3 = bithermic
4=instant with solar power input
5 = open vent
6 = boiler with heat pump
0
PAR 03 Gas Type Configuration
0 = G20; 1 = G31; 2 = G230
0 or 1 or 2
To enter "Parameter setting and display"refer to the indications
provided in the specific section.
Once the parameters in the table have been set, you must carry
out the entire phase of "Self-calibrating procedure" described
in the specific section.
If the
gas valve
and/or the
ignition/detection electrode
, and/or the
burner
, and/or the
fan
are replaced, the user must still carry out
the entire phase of "Self-calibrating procedure" described in
the specific section.
4.6
Malfunction codes and possible solutions
LIST OF MALFUNCTION/FAULT ALARMS
Type No. Fault
Solution
ALL
01 Smoke thermostat
- Contact the Technical
Assistance Centre
ALL
02 Low water pressure in
system
- Restore pressure
- Check for any leaks in the
system
ALL
03 High water pressure in
system
- Empty the system via the
drain valve on the hydraulic
assembly and bring the
pressure to approximately
1.2 bar
ALL
04
Domestic hot water
sensor fault (return
sensor fault for T
models)
- Check connections
- Check the sensor is working
ALL
05 Delivery sensor fault
- Check connections
- Check the sensor is working
ALL
06 No flame detection
- Check the integrity of the
electrode and check that it is
not grounded
- Check gas availability and
pressure
- Check the integrity of the gas
valve and the card
ALL
07 Sensor or safety
thermostat intervenes
- Check the sensor or
thermostat connections
- Deaerate the system
- Check the bleed valve
- Replace the sensor or the
thermostat
- Check that the pump impeller
is not blocked
ALL
08 Fault in the flame
detection circuit
- Check the integrity of the
electrode and check that it is
not grounded
- Check the integrity of the gas
valve and the card
Type No. Fault
Solution
ALL
09 No water circulating in
the system
- Check the rotation of the
pump rotor
- Check the electrical
connections
- Replace the pump
ALL
10 Auxiliary sensor fault
- Check PAR 02 "hydraulic
configuration"
- Check the electrical
connection
ALL
11 Gas valve modulator
disconnected
- Check the electrical
connection
ALL
12 Domestic hot water
sensor fault in tank mode
- Set the parameter
PAR 04 (Combustion
configuration) to 0
ALL
13 Smoke probe intervention
- Check the sensor is
working
- Replace the smoke probe
ALL
14 Smoke probe fault
- Replace the smoke probe
- Check the electrical
connection of the smoke
probe
- Contact the Technical
Assistance Centre
ALL
15 Fan check cable
disconnected
- Check the connection
cable between the fan and
the board
ALL
18 Condensate level fault
- Check for any clogging in
the pipe which takes the
condensate to the siphon
- Check that the siphon is
not clogged
ALL
28
Maximum number of
consecutive resets
reached
- Wait 1 hour and try
unblocking the board
again
- Contact the Technical
Assistance Centre
ALL
30 Return sensor fault (boiler
sensor fault for T models)
- Replace the return probe
- Check parameters
- Contact the Technical
Assistance Centre
ALL
37 Fault due to low network
voltage
- Check the voltage
- Contact your network
provider
ALL
40 Incorrect network
frequency detected
- Contact your network
provider
ALL
41 Flame loss more than 6
consecutive times
- Check the ignition/
detection electrode
- Check the gas supply
(open valve)
- Check mains gas pressure
ALL
42 Button fault
- Check that buttons are
working
ALL
43 Open Therm
communication fault
- Check the OT electric
connection
ALL
44 Gas valve timeout fault
without flame
- Check gas valve and board
ALL
56
Lock for
∆T
delivery/
return over max limit
(open vent)
- Contact the Technical
Assistance Centre
ALL
57 Lock for flow temperature
(FT) check (open vent)
- Contact the Technical
Assistance Centre
ALL
62 Self-calibrating procedure
is required
- Carry out the self-
calibrating procedure (see
the specific section)
ALL
72 Incorrect positioning of
the delivery sensor
- Check delivery sensor
operation and position
ALL
74 Second delivery sensor
fault
- Check second delivery
sensor operation and
position
ALL
77 EV2 SGV current max/min
absolute limits error
- Check gas valve and board
ALL
78 EV2 SGV current upper
limit error
- Check gas valve and board
ALL
79 EV2 SGV current lower
limit error
- Check gas valve and board
ALL
80
Fault on the valve control
logic line/valve cable
damaged
- Check gas valve and board