Table A-5
Environmental Specifications (Single M-Rack)
Feature
Specification
Temperature tolerance
(operating with 95-Watt
processors)
+5
C (41
F) to +35
C (95
F) (up to 1500 m / 5000 ft.)
+5
C (41
F) to +30
C (86
F) (1500 m to 3000 m /5000 ft. to 10,000 ft.)
Temperature tolerance
(operating with 135-Watt
processors)
+5
C (41
F) to +28
C (82.4
F) (up to 1500 m / 5000 ft.)
+5
C (41
F) to +23
C (73.4
F) (1500 m to 3000 m /5000 ft. to 10,000 ft.)
Temperature tolerance
(non-operating)
-40
C (-40
F) to +60
C (140
F)
Relative humidity
10% to 95% operating (no condensation)
10% to 95% non-operating (no condensation)
Rack cooling requirements
Chilled water cooling
Heat rejection (dissipation)
to air
Zero BTUs
Heat rejection (dissipation)
to water
Approximately 246 kBTU/hr maximum (21 tons) (based on 100%
dissipation to water)
Maximum altitude
10,000 ft. (3,049 m) operating
40,000 ft. (12,195 m) non-operating
M-Cell rack acoustical noise
level (sound power)
Approximately 80 dBA (at front of system)
Cooling distribution rack
(CDU) acoustical noise level
(sound power)
Approximately 65 dBA (at front of unit)
System-level Specifications
007-5806-004
111
Summary of Contents for ICE X
Page 1: ...SGI ICE X System Hardware User Guide Document Number 007 5806 004 ...
Page 4: ......
Page 10: ......
Page 14: ......
Page 27: ...Powering the System On and Off 007 5806 004 7 Figure 1 5 Three Phase PDU Examples ...
Page 36: ......
Page 78: ...58 007 5806 004 4 Rack Information Figure 4 2 Front Lock on Tall 42U D Rack ...
Page 80: ...60 007 5806 004 4 Rack Information Figure 4 4 Air Cooled D Rack Rear Door and Lock Example ...
Page 84: ...64 007 5806 004 4 Rack Information Figure 4 6 SGI ICE X Multi Cell M Cell Rack Array Example ...
Page 86: ......