MAINS FAILURE   

 

  

CONFIRM     

      

 

 

 

      MAINS FAILURE     N 

 

  

  

T : 30 min.              

       

     

 

 

Activate the function changing N 

(no) in Y (yes) using the buttons ↑↓. 

Insert the delay after which we 

wanna have the message 

      MAINS FAILURE    Y 

 

  

  

T : 05 min:           

         

     

 

 

 
4.9.4) PERIODIC CALL:

 follow the vocal instructions for the SMS 

– look also 2.2.2 

 

PERIODIC CALL       

 

  

CONFIRM        

       

 

 

 

PERIODIC CALL       N  

 

  

T : 24 h          00 :00  

      

 

 

 

Enable the function changing N (no) 

in Y (yes) using the buttons ↑↓. 

Insert the delay after which we 

wanna have the message (hours) 

   PERIODIC CALL     Y 

 

  

  

T : 24 H     10.00

        

     

 

 

4.9.5) SIM VALIDITY:

 follow the vocal instructions for the SMS 

– look also 2.2.2 

 

    SIM  VALIDITY         

 

  

  

CONFIRM           

        

     

 

 

    SIM VALIDITY       N  

 

  

  

T : 11 month       

         

     

 

 

Enable the function changing N (no) 

in Y (yes) using the buttons ↑↓. 

Insert the delay after which we 

wanna have the message (hours) 

    SIM VALIDITY      Y  

 

  

  

T : 10 month 

              

     

 

 

4.9.6) TIME/DATE:

 updating the internal clock and date is important for the historic memory of the events. Internal clock - precision: the adopted 

technical solutions may cause a flexibility up to 2 seconds per day, which should be adjusted during the system periodical check, at least every 
6 months. 

       TIME AND DATE       

 

  

  

CONFIRM

                  

     

 

 

SET   TIME 

19.25 

 

 SET DATE 

DD / MM / YY 

 

 

  

 

 

 

4.9.7) TELEPHONE EXCHANGE (PABX): 

function not present. 

 

4.9.8) INSTALLER CODE

useful function for seeing/changing this code

 

 

       INSTALLER CODE   

 

  

  

CONFIRM

                  

     

 

 

     INSTALLER CODE   

 

   

  

2222         

                 

     

Press 

← ←  ← ←  to cancel the code and enter the new 

Warning: to restore a missing code, cut power supply, open the unit 

(tampering alarm) and disconnect battery. Replace after 10 sec. and 

enter the factory code 0 0 0 0. 

 

 

4.9.9) ANTISCANNER

: the control unit checks the radio signals in the ether and signals those which interfere with functioning. It is possible to 

set the time of the interference that can be ignored in seconds (1-60), exceeding which the siren is triggered in the control unit and current is 
found at the SIR terminals. 

Attention !

 Reduced time get faster communication of radio interference, that can depends by Tamper attempts  or occasional interference  in 

the ether, 

and so that to don’t care: for this reason the control panel will present a pre-programmed time of 60 secondes, a right delay for the 

function target. 

       ANTISCANNER         

 

  

  

CONFIRM

                  

     

 

 

       ANTISCANNER    N  

 

  

  

T: 60 SEC.

                

     

 

 

Choose Y (yes) or N (no) to set the 

function and write timing of 

signalled noises 1-99 sec. 

      ANTISCANNER    Y  

 

  

  

T: 90 SEC.

                

     

 

 

4.9.10)

 

SUPERVISION

: supervision is the transmission of the operating status that every peripheral device transmits approx. every 40 minutes: 

the absence of 8 consecutive signals (over 5 hours) from a peripheral device causes the signal of the phenomenon with every arming/disarming 
of the system.  Such communication identify the necessity of a functionality control of the device (TEST).   

       SUPERVISION          

 

  

  

CONFIRM

                  

     

 

 

     SUPERVISION       N   

 

  

  

CONFIRM

                  

     

 

 

Choose Y (yes) or N (no)      

to set the function 

 

 

  

 

 

4.9.11)

 

EXIT TIME

:  Attention! Times too short do not allow service communications that take place during this time, for this reason we suggest 

to program at least 60 seconds, as the device automatically propose. 

Summary of Contents for SERENYA 2000

Page 1: ...COPYRIGHT SERENYA COD 2001 SERENYA by Silentron made in Italy SERENYA MIX GSM cod 2001 Mixed wired wireless control panel with GSM telephone transmitter ...

Page 2: ...tions It is mandatory to dispose of accumulators waste batteries according to the Standards in force This is also the case when the devices must be scrapped The batteries must be previously removed returning them to the seller or depositing them in the relevant containers made available by the distribution network If liquid should escape from the batteries use silicone gloves to protect the hands ...

Page 3: ... 1 2 ARMING DISARMING DEVICES it s possible to program up to 10 key fobs and an unlimited number of keypads look Warning SERENYA control panels can be commanded trought the on board keypad or trought bidirectional key fobs Code 2023 and or trought bidirectional keypads Code 2028 qui confirment les opérations effectuées Soit les télécommandes que les claviers disposent de touches fonction pour acti...

Page 4: ...en a transmitter detectors key fobs keypadss and a receiver control panel sirens In our case because of the low transmission power imposed by the Rules the radio range can change a lot especially inside environments where the position of the transmitter in relation to the receiver is basical Besides walls and furniture sometimes create reflections of the radio signals increasing or reducing the ra...

Page 5: ...y arming 2 2 Bidirectional telephone part Telephone calls In the installation phase the relevant messages must be recorded written and connected to telephone numbers to call in the event of alarms for example the ALARM will be connected to user family or friend s numbers numbers of intervention forces It is useless to connect the installer s number to the alarm calls while it is useful to connect ...

Page 6: ... generating a Tamper alarm disconnect and connect again power supply and begin entering the factory code this operation doesn t delete the realized programming a INSTALLER CODE from 4 to 8 digits which allows access to all programming but not operations b USER CODE from 4 to 8 digits it allows the followings functions placing the control unit in TEST mode for testing or battery change reading the ...

Page 7: ...ssible tests C1 and C2 identify the received signal level no indication zero Detectors test look remark simulate an alarm condition for every detector individually ALARM det name 03 C1 H C2 H ALARM is the alarm transmission TAMPER in case of tempering A01 is the detector identification if a name hasn t been associated to The other indications are the same of before The quality of the radio signal ...

Page 8: ...all done KO failed call OC line busy NO no answer READING THE EVENTS WITH CONTROL MANAGEMENT 13 02 09 10 10 INSTAL Date and time of the event INSTAL installer access USAGER USER access GSM no GSM field NUM MOD telephone number changement GSM TEST automatic Restart operation of the GSM module READING THE ALARMS 13 02 09 10 10 ARMED JOHN Date and time of the event ARM total arming ARM AB armed parti...

Page 9: ...ll press ESC or the button 3 3 10 OTHER FUNCTIONS OF THE CONTROL PANEL Control units with a GSM module offer other automatic functions which can be programmed during installation periodic transmission of control unit operational status SMS GSM models only communication of SIM expiry it is recommended to use SIM without expiry SMS notification of failure and reinstatement of electrical mains power ...

Page 10: ...ADD NAME PHILIP PHILIP 01 555666777888999 Confirm delete CANC or modify selected name and number VOCAL MESSAGES 2 3 6 Confirm delete CANC or modify the association numbers messages Using buttons from 1 to 6 PHONE BOOK CONFIRM MEMORY CONFIRM 01 SEARCH POSIT CONFIRM ADD POSITION 01 PHILIP 01 555666777888999 Confirm delete CANC or modify selected name and number VOCAL MESSAGES 2 3 6 Confirm delete CA...

Page 11: ...te it only to the number of the interested doctor MSG 5 Attention technical problem at M Rossi s house via Bianchi 10 Turin it will be added fire detector flooding or other depending by the association MSG 6 Attention message from M Rossi s house via Bianchi 10 Turin change the battery the name of the device will be added it will be control panel for the battery of the control panel 4 6 2 VOCAL ME...

Page 12: ...itions Use 1 2 3 4 5 6 to modify the managed partitions ENTER CODE 4 5 6 7 8 example Enter a 5 digits code 45678 ON A B C MEMOR OFF A B C LABEL CODE 01 _ _ _ _ _ _ _ _ _ _ _ _ _ Write the name of the CODE owner UNDER THREAT N CONFIRM Enable the UNDER THREAT function for the code Y yes or N no VOCAL LABEL TO RECORD Talk close to the microphone Press for all the recording time Verify the remaining t...

Page 13: ...ways shows the first free position Selecting a previous position the already programmed devices will appear Confirm the one to be modified and procede or delete pressing CANC and re program it 4 9 SETTINGS in this section we can program certain particular functions of the control panel Scroll the different functions using buttons 4 9 1 DETECTOR EXCLUSION EXCL SENSORS CONFIRM A 01 KITCHEN CONFIRM S...

Page 14: ...tore a missing code cut power supply open the unit tampering alarm and disconnect battery Replace after 10 sec and enter the factory code 0 0 0 0 4 9 9 ANTISCANNER the control unit checks the radio signals in the ether and signals those which interfere with functioning It is possible to set the time of the interference that can be ignored in seconds 1 60 exceeding which the siren is triggered in t...

Page 15: ...4 9 16 FW VERSION display of the control unit version for any interventions FW VERSION CONFIRM FW VERSION 30155 4 9 17 SYSTEM RESET Confirmation of CANCEL results in the erasing of all the programming performed and of the events memory Be careful before confirming this operation which is irreversible SYSTEM RESET CONFIRM DELETE CONFIRM 4 10 PROGRAMMING THE ALARM DEVICES WIRELESS WARNINGS look spec...

Page 16: ...5mA in stand by and no wired connections 125mA with backlighting of the display 500mA in alarm Autonomy approx 36 hours with charged battery in stand by and without wired connections To determine the autonomy in the presence of wired connections measure the absorption of the battery without 230V and calculate it correctly Alarm inputs up to 50 instant programmable detectors delayed or AND on 3 arm...