Electrical installation
Instruction Manual OilGuard 2 Ex
13003E/3
35
5.2
Connecting the mains voltage to the Ex control unit
WORKSTEP
ADDITIONAL INFO / IMAGES
1.
Loosen the four screws (circles) and remove the
cover on the Ex control unit.
2.
Loosen the left cable gland (circle) and feed the
mains cable into the Ex control unit.
3.
Connect the power supply to the terminals ac-
cording to the following table.
Terminals Function
18 (L)
Phase
16 (N)
Neutral
PE
Protective
earth (arrow)
4.
Tighten the cable gland.
5.
Close the Ex control unit.