10
9900 Transmitter
Terminals 1-2: DC Power
Required by the instrument
●
10.8 to 35.2 VDC input power to sensors, relays and the LCD backlight
Terminals 3-4: Loop Power (may also be used for system power)
●
10.8 to 35.2 VDC
NOTE:
Backlight, LEDs and optional Relay Module do not operate on
loop power. Any connected sensors or sensor electronics that cannot
operate on loop power will also be inoperative.
Terminals 5-6: Open Collector
●
Software selectable for Normally Open or Normally Closed.
●
May be disabled (Off) if not used.
Terminals 7-10: Digital (S
3
L)/Frequency Input
7: V+: +5 VDC out to sensor (black wire)
8: DATA: Input signal from sensor (red wire)
9: GND: Sensor ground (white wire)
10: SHLD: Cable shield
The 9900 requires regulated
10.8 to 35.2 VDC (24 VDC nominal)
from an external power supply (not supplied).
Maximum current draw is:
200 mA
= 9900 without Relay module
300 mA
= 9900 with Relay module
When connecting a non-Signet sensor to the 9900, the sensor’s 4 to 20 mA signal must be
converted to Digital (S
3
L). The 8058 i-Go Signal Converter accepts any 4 to 20 mA signal
and converts it into Digital (S
3
L).
1. Wire the 8058 between the 4 to 20 mA loop source and the 9900 Digital (S
3
L) input
terminals (see page 14).
2. In the 9900 INPUT TYPE menu (see System Setup Menu discussion, page 25),
specify 4 to 20 mA INPUT.
3. Set additional labels and abbreviations as described on pgs. 42-43.
Signet 8058 i-Go™
4-20 mA to S
3
L Converter
+GF+
4-20 mA input
S
3
L Output
Input
4-to-20 mA
Output
S
3
L
White
Shield
Shield
Black
Black
Red
Red
8058-1
4-20 mA
Input
N
/C
3
Lo
op
1 -
2
Lo
op
1 +
1
+GF
+
S L
Output
3
7 +
5V
D
C
8
S L
9
GND
3
8058 i-Go™
4-20mA
to S
3
L
Converter
3-8058.610D
35V
DC
MA
X
N
/C
6
Lo
op
2 -
5
Lo
op
2+
4
3 2 1
6 5 4
7 8 9
Loo
p1
PW
R
+G
F+
N/C
S L
DATA
3
Loo
p2
PW
R
Sig
net 80
58
8058-2
For the 8058-2,
connect Channel 1
ONLY
10
9
7 8
V+
DA
T
A
GND
SHLD
Digital (S
3
L)/Freq
1
2
3
4
5
6
PWR+
PWR–
Loop+
Loop–
OC-
OC+
Power
Signal Type: 4 to 20 mA
Terminal Identi
fi
cation