NOTE:
This screen sets what the Myriad ROS displays in its ‘default screen’ for the selected input.
The default shown above will display 0.0 units when the input is 4.00 MA. Both the input and the
display can be changed for different requirements.
A) With the cursor selecting ‘INPUT = 4.00’ use the buttons to change the input value for the
required displayed value.
B) Use the buttons to move the cursor to the ‘display’ value and the Up/Down buttons to
change the desired display for the previously selected input. Once complete, scroll to ‘SAVE’, press
‘ENTER’ to access ‘INPUT SCALE 2’ screen.
Follow the steps outlined above to set the values of ‘input’ and ‘display’ for input Scale 2.
NOTE: IF THE APPLICATION IS A LINEAR ONE BETWEEN THE INPUT SIGNAL MIN. TO
MAX. VALUES THEN HIGHLIGHT THE ‘DONE’ ITEM AND PRESS ‘ENTER’ TO SAVE THE
SCALED VALUES.
ENGINEERING UNITS SELECTION:
When ‘Scale Menu’ is complete the ‘INPUT TEXT” menu is the last menu in the scaling process.
This screen allows the selection of several engineering units. With the cursor on the default value as
shown, press the Up/Down buttons to select between
‘GPM’
‘FT’
‘IN’
‘HZ’
‘%’
‘GAL’
‘LTR’
Use the
↑
↓
keys to select the desired engineering units then with the
→
←
keys, highlight ‘NEXT’ and
press ‘ENTER’ to access the “display filter” screen.