MENU 2 DIGITAL OUTPUT PROGRAMMING
The Myriad ROS has 2 solid state outputs, which can be configured to set ‘TURN ON’ and reset ‘TURN
OFF’ at a user defined value of the input. From Menu 1 select ‘OUTPUTS’ and press ‘ENTER’.
Using the buttons scroll to the value at which the output ‘SETS’ or turns on, with this value highlighted,
use the Up/Down buttons to enter a value of input to activate the output. Scroll down to the ‘RESET’
point and again change this value to input value, which will turn the digital OUTPUT 1 off.
NOTE: The internal HORN will sound when the output setpoint is reached. To prevent the horn
from sounding, highlight the ‘Y’ symbol adjacent to the horn symbol and use the Up/Down buttons
to change the value to ‘N’ (NO). This will prevent the horn from sounding when the setpoint is
reached.
Once all values are selected, scroll to ’NEXT’ press ‘ENTER’ to move to the #2 setpoint screen and
proceed as described above.
When both setpoints are configured, scroll to ‘EXIT’ and press ‘ENTER’ to return to the ‘Main Menu’.
Select the ‘CLR’ to reset these values to the current process value and ‘EXIT’ and ‘ENTER’ to return to
the main screen.