background image

 

 

 

20

 

Fault code 06/58 

Output abnormal (Inverter voltage   

is over 150Vac or below 40Vac). 

1.Reduce the connected load. 

2. Restart the unit, if the error happens again, please   

return to repair center. 

Fault code 07 

The inverter is overload 110% and   

time is up. 

Reduce the connected load by switching off some   

equipment. 

Fault code 08 

Bus voltage is too high. 

1.If you connect to a lithum battery without 

communication, check whether the voltage points of   

the program 19 and 21 are too high for the lithum   

battery. 

2. Restart the unit, if the error happens again, please   

return to repair center. 

Fault code 09/53/57 

Internal components failed. 

Restart the unit, if the error happens again, please   

return to repair center. 

Warning code 15 

The input status is different in   

parallel system. 

Check if AC input wires of all inverters are   

connected well. 

Warning code 16 

Input phase is not correct. 

Change the input phase S and T wiring. 

Warning code 17 

The output phase not correct in   

parallel. 

1.Make sure the parallel setting are the same   

system(sigle or paralle; 3P1,3P2,3P3). 

2.Make sure all phases inverters are power on. 

Warning code 20 

Li battery can't communicate to the   

inverter. 

1.Check whether communication line is correct   

connection between inverter and battery. 

2.Check whether BMS protocol type is correct setting. 

Fault code 51 

Over current or surge. 

Restart the unit, if the error happens again, please   

return to repair center. 

Fault code 52 

Bus voltage is too low. 

Fault code 55 

Output voltage is unbalanced 

Fault code 56 

Battery is not connected well   

or fuse is burnt. 

If the battery is connected well, please return to   

repair center. 

Fault code 60 

Negative power fault 

1.

 

Check whether the AC output connected to the grid 

input. 

2.

 

Check whether Program 8 settings are the same for   

all parallel inverters 

3.

 

Check whether the current sharing cables are   

connected well in the same parallel phases. 

4.

 

Check whether all neutral wires of all parallel units   

are connected together. 

5.

 

If problem still exists, contact repair center. 

Fault code 80 

CAN fault 

1.

 

Check whether the parallel communication cables 

are connected well. 

2.

 

Check whether Program 23 settings are right for the 

parallel system.

 

3.

 

If problem still exists, contact repair center 

Fault code 81 

Host loss 

 

Note: 

To restart the inverter, all power sources need to be disconnected. After the LCD screen light is off, only use the battery to 

restart the inverter. 

 

5 Warranty 

We warrant this product against defects in materials and workmanship for a period of one year from the date 
of purchase and will repair or replace any defective M Series Inverter when directly returned, postage 
prepaid, to manufacturer. This warranty will be considered void if the unit has suffered any obvious physical 
damage or alteration either internally or externally and does not cover damage arising from improper use 
such as plugging the unit into an unsuitable power sources, attempting to operate products with excessive 
power consumption requirements, reverse polarity, or use in unsuitable climates. 
WARRANTY DOES NOT INCLUDE LABOR, TRAVEL CHARGES, OR ANY OTHER COSTS 
INCURRED FOR REPAIR, REMOVAL, INSTALLATION, SERVICING, DIAGNOSING OR 
HANDLING OF EITHER DEFECTIVE PARTS OR REPLACEMENT PARTS. THE WARRANTOR 

Summary of Contents for MCRLCD

Page 1: ...s Manual For Solar Inverter Models M3024NC M3048NC M3048BP M5000H 48BP M6048DUL M12048DUL etc Version 1 0 PN MCRLCD220509 Manufacturer Information Sigineer Power Limited Email info sigineer com TEL 8...

Page 2: ...ecting to Inverter 4 2 6 LCD Specification Setup 4 4 Maintenance Troubleshooting 16 5 Warranty 20 Please record the Sigineer Power unit s model and serial number in case you need to provide this infor...

Page 3: ...use this remote LCD panel on other equipments it is designed only to work with Sigineer Power solar inverters produced after 2022 May 2 Don t use any third party communication cables on the panel 3 D...

Page 4: ...ection Unit x1 User manual x 1 Communication cable 20m 65 6ft x 1 2 4 Installation There are two pieces of flanges which can be flexibly installed either on the panel top or two sides Surface Mounting...

Page 5: ...3 Flush Mounting with Flange on the Sides...

Page 6: ...el area includes three LED indicators four function keys and a LCD display It shows very rich operating info 1 LCD display 2 Status indicator 3 Charging indicator 4 Fault indicator 5 Function buttons...

Page 7: ...ppened Indicate short circuit happened Battery Information Indicate battery level by 0 24 25 49 50 74 and 75 100 in battery mode and charging status in line mode Indicate battery voltage battery perce...

Page 8: ...wer Indicates the utility charger circuit is working Indicates the DC AC inverter circuit is working These three signs indicate the output priority SOL FIRST indicates solar first BAT FIRST indicates...

Page 9: ...Utility Battery In this mode the inverter will transfer between DC and AC as per the settings of program 12 and 13 Users can set it to utility priority to stop the cycling 01 SbU SBU Priority As indi...

Page 10: ...P 95 140Vac 7V M5000H 48BP 170 280VAC 7V M6048DUL M12048DUL 184 272Vac 7V 03 GEN In Generator Mode the acceptable AC input voltage range M3024NC M3048NC M3048BP 65 140Vac 7V M5000H 48BP 90 280VAC 7V M...

Page 11: ...only when the battery voltage changes big enough Due to the ripple current from the utility charger when US2 is set for charging lithium batteries it is recommended to set the max utility charging cur...

Page 12: ...nt is set according to Program 02 for utility charger Program 12 DC to AC Transfer Voltage The setting works when program 01 is in SBU Priority or Solar Priority Mode Model Default Value Resettable Ra...

Page 13: ...the charger Program 20 Float Charging Voltage Model Default Value Resettable Range 48V Models 54V 48V 58 4V If user defined setting USE US2 is selected in program 5 this program can be set up Program...

Page 14: ...Charging Current Max PV Utility Charging Current 03 AC Input Voltage Range Appliance Mode Default 03 AC Input Voltage Range UPS Mode 03 AC Input Voltage Range Generator mode 04 Power Saving Mode Savi...

Page 15: ...rity Solar Priority 14 Charger Power Source Priority Solar and Utility Default 14 Charger Power Source Priority Solar Only 15 Alarm On Off Control Audible Alarm on default 15 Alarm On Off Control Audi...

Page 16: ...oltage Load percentage PV input voltage Battery voltage Warning or Fault code Default Display Screen AC Input frequency Output frequency Load power in VA PV energy sum in KWH Battery percentage Warnin...

Page 17: ...erter can charge battery without AC output Power saving mode If enabled the output of inverter will be off when connected load is two low or not detected No output is supplied by the unit but it still...

Page 18: ...rger switch to DC to AC model The M5000H 48BP inverters can be stacked up to 6 pcs to expand output power in 230Vac or create 230 400Vac three phase The M3048BP can be stacked up to 6 pcs to expand ou...

Page 19: ...9 Bus soft start failed 51 Over current or surge 52 Bus voltage is too low 53 Inverter soft start failed 55 Over DC voltage in AC output 56 Battery connection is open 57 Current sensor failed 58 Outpu...

Page 20: ...Beep once every second 16 Parallel input phase error Beep once every second 17 Parallel output phase loss Beep once every second 18 Buck over current Beep once every second 19 Battery disconnect No b...

Page 21: ...es are too thin and or too long 2 Check if generator if applied is working well or if input voltage range setting is correct UPS Appliance Green LED is flashing Set Battery First or Solar First as the...

Page 22: ...ery is not connected well or fuse is burnt If the battery is connected well please return to repair center Fault code 60 Negative power fault 1 Check whether the AC output connected to the grid input...

Page 23: ...lly or externally or damaged from improper use or use in an unsuitable environment violations of the warnings in the manual will invalid the warranty b the product if it has been subjected to fire wat...

Reviews: