![Sifam Tinsley ND20LITE User Manual Download Page 59](http://html.mh-extra.com/html/sifam-tinsley/nd20lite/nd20lite_user-manual_1267046059.webp)
59
Power input:
- in supply circuit
6 VA
- in voltage circuit
0.05 VA
- in current circuit
0.05 VA
Display field:
dedicated display LCD 3.5’’
Realay output:
relay, voltageless NO contacts
load capacity 250 V~/ 0.5 A ~
Serial interface RS-485:
address 1...247;
mode: 8N2,8E1, 8O1,8N1;
baud rate: 4.8, 9.6, 19.2, 38.4 kbit/s
transmission protocol: Modbus RTU
response time: 600 ms
Energy impulse output
output of OC type (NPN), passive
of class A , acc.to EN 62053-31
supply voltage18 .. 27 V,
current 10 .. 27 mA
Constant of OC type
output impulse:
1000 - 20000 imp./kWh
independently of set tr_U, tr_I ratios
Protection grade ensured by the casing:
- from frontal side
IP 65
- from terminal side
IP 20
Weight
0.3 kg
Overall dimensions
96 x 96 x 77 mm
Summary of Contents for ND20LITE
Page 2: ...2 ...
Page 4: ...4 ...
Page 18: ...18 6 4 Operating modes Fig 6 Operating modes of the ND20LITE meter 7 ...
Page 27: ...27 a n on b n off ...
Page 63: ...63 ...