4005
RW
0..3
Synchronization of mean active
power:
0 – 15 minutes’ walking window
(record synchronized every 15
minutes with the clock)
1 – measurement synchronized
every 15 minutes with the clock
2 – measurement synchronized
every 30 minutes with the clock
3 – measurement synchronized
every 60minutes with the clock
0
4006
RW
0
reserved
0
4007
RW
0,1
Storage way of minimum and
maximum values
0 – without errors,
1 – with errors
0
4008
RW
0,1
Way to calculate reactive power:
0:
2
2
P
S
Q
-
=
1:
(
)
i
i
k
i
i
i
I
U
I
U
Q
,
sin
*
*
1
∠
=
∑
=
k – harmonic number,
k = 21 for 50 Hz,
k = 18 for 60 Hz
0
4009
RW
0,1
Way to calculate reactive energy:
0 – inductive and capacitive
energy
1 – positive and negative energy
0
4010
RW
0...61
Display backlit:
0 – disabled,
1-60 – backlit time in seconds
since the push-button pressure,
61 – always enabled
61