background image

Model 4105 Gas Sensor Module (12/02)

Page:  2

 Instruction Manual

2.

CAUTIONS WARNINGS &
RECOMMENDATIONS

2.1 INTRODUCTION

Although the sensor module is designed and con-
structed for installation and operation in industrial
applications including “hostile” environments, cau-
tion should be taken to insure that the installation is
in compliance with this instruction manual and that
certain procedures and conditions are avoided.

READ AND UNDERSTAND THIS INSTRUCTION
MANUAL BEFORE OPERATING OR SERVICING
THIS EQUIPMENT.

2.2 WIRING

Electro magnetic and radio frequency interference to
the analog communication between the sensor and
the controller may occur.  The manufacturer recom-
mends that extra caution be taken where the installa-
tion is near any sources of these interferences:

Avoid running sensor cable close to high power
cables, radio transmission lines, or cables subject to
pulses of high current.  Avoid running cables near
large electric motors or generators.

Use shielded cable in any location which may be ex-
pected to be electrically noisy or where cable is ex-
pected to be in close contact with AC wiring.  The
shield should be connected to the controller com-
mon, one side only.

The wiring should be run in either a cable tray or
conduit as required by applicable code and area clas-
sification.  Control wiring should not be installed in a
cable tray or conduit with higher voltage and AC cir-
cuits.  See Table 2.1 for recommended wire gauge.

Wiring connections at the gas sensor module are as
follows:

Wire#

Function

Terminal

1

Power

PWR

2

Signal

SIG OUT

3

Ground

GND

Connect an earth ground to the ground screw pro-
vided in the base of the gas sensor module enclo-
sure.

All splices must be via either a lug and terminal sys-
tem or soldered.  Improperly spliced cable can result
in corrosion, resistance changes and system errors.

Wire Gauge

Maximum Length

20 AWG

2,000 Ft.

18 AWG

3,000 Ft.

16 AWG

4,000 Ft.

14 AWG

6,500 Ft.

12 AWG

9,000 Ft.

Table 2.1

Recommended Wire/Cable Gauge

NOTE:

  Temperature rating of cable wire insulation

must be above 75oC (85oC or greater rated wiring is
recommended).  If cable runs through higher tempera-
ture environments, it should be specified for that en-
vironment.

2.3 SENSOR MODULES - GENERAL

Sensors should be facing down.  Avoid installing sen-
sor modules where they will be unnecessarily exposed
to wind, dust, water (esp. direct hose down), shock,
or vibration.  Observe temperature range limitations.

Sensors may be adversely affected by prolonged ex-
posure to certain materials.  Loss of sensitivity, or
corrosion, may be gradual if such materials are present
in low concentrations.  These materials include: Ha-
lides (compounds containing chlorine, fluorine, bro-
mine, or iodine),  silicones, acid vapors, caustic liq-
uids or vapors.

Sensor modules must not be painted

.  Paint may con-

tain compounds which will contaminate the sensor.
Paint will also cause clogging of the sintered metal
cup and will cause difficulties during attachment of
the calibration fitiing.  The module should be tagged
“DO NOT PAINT”.

When sensors are replaced the thread on the sensor
housing 

must be lubricated with an antizieze com-

pound non-silicone based 

 to avoid metal to metal

binding which will damage the housing threads.

2.4 PREVENTATIVE MAINTENANCE

DUST AND DIRT CONTROL:  When calibration is
performed the controller and sensors should be
checked visually to determine if dust or dirt build up
needs to be removed.  This cleaning should be done
with dry instruments such as compressed air, cloth
wipes or wisk broom.

WIRING OR CABLE CONDITIONS:  Any wiring or
cables which are not in conduit should be checked
once a year for damage to insulation or corrosion
of splice or terminal points.

Summary of Contents for 4105 SERIES Applicability & effectivity

Page 1: ...MODEL 4105 SERIES GAS SENSOR MODULE WITH DIGITAL DISPLAYAND NON INTRUSIVE CALIBRATION 4 20 mA...

Page 2: ...n 4105 05 Hydrogen Sulfide Gas Sensor Module with Non Intrusive Calibration 4105 06 Chlorine Gas Sensor Module with Non Intrusive Calibration 4105 07 Hydrogen Gas Sensor Module with Non Intrusive Cali...

Page 3: ...Transmitter Installation 3 3 6 Start up Operation 3 4 OPERATION 4 4 1 Introduction 4 4 2 Signal Value 4 5 CALIBRATION 5 5 1 Frequency of Calibration 5 5 2 Calibration Process 5 5 3 Equipment Required...

Page 4: ...which contains the transmitter electronics and a gas sensor which is installed in one of the two 3 4 conduit hubs 1 3 1 Electronics When installed the transmitter electronics will be con nected to a p...

Page 5: ...soldered Improperly spliced cable can result in corrosion resistance changes and system errors Wire Gauge Maximum Length 20AWG 2 000 Ft 18AWG 3 000 Ft 16AWG 4 000 Ft 14AWG 6 500 Ft 12AWG 9 000 Ft Tab...

Page 6: ...e moval and replacement of the sensor assembly which is threaded into the second 3 4 conduit hub 3 4 Wiring Connection To gain access to the I O PCB for wiring or mounting purposes loosen the two capt...

Page 7: ...r failure occurs Periodic cleaning as necessary Unanticipated maintenance 4 2 Signal Value During normal operation the current loop of the sen sor module and the controller will be between 4 mA indica...

Page 8: ...tic tool provided with each sensor Briefly hold the magnet tool close to the small dot located on the lower edge of the front panel The arrow on the upper left side of the LED will illuminate and the...

Page 9: ...new transmitter 7 Restore power and allow a minimum of 30 minutes for stabilization before re calibration 6 4 Sensor Replacement The sensor should be replaced when it is determined that It is no long...

Page 10: ...output at 0mA These conditions remain until the FAULT is corrected 6 4c Electrochemical Oxygen and Toxics Verify that the voltage VOUT is equal to the volt age as desired The VOUT test point on the I...

Page 11: ...facing vertically down The lid of the sensor module should face out for easy access Sensors may be mounted directly onto the end of a vertical conduit or bracketed to a vertical surface us ing the tw...

Page 12: ...VOLTS BAL R 2 R11 U1 Sensor Pwr Sig Black Brown Red Toxics P1 TB1 TB2 RIBBON CABLE TO CPU ASSY VOUT JP2 B A JP1 1 3 2 4 U2 U7 U4 U5 U1 S C R R19 ST 46A EC I O PCB FOR ELECTROCHEMICAL SENSORS Sensor Pw...

Page 13: ...F 14 to 122o F 14 to 122o F 14 to 122o F 14 to 122o F 10 to 75o C 7 to 50o C 10 to 50o C 10 to 50o C 10 to 50o C 10 to 50o C 10 to 50o C Relative Humidity 10 95 5 99 15 90 15 90 15 90 10 90 15 90 Pre...

Page 14: ...0 to 50o C 10 to 50o C 10 to 50o C 10 to 45o C 10 to 45o C Relative Humidity 15 90 15 90 15 90 20 90 20 90 Pressure 10 10 10 10 10 Electrical Data Input Voltage DC 19 30 VDC at less than 100 mA Output...

Page 15: ...0 55 30 2 40 50 4105 05 H2 S 0 5 100 20 0 1 15 15 0 0 0 0 4105 06 Cl2 0 10 100 0 0 105 0 0 0 0 4105 07 H2 1 20 0 100 3 0 35 3 35 85 4105 10 SO2 1 0 40 0 100 100 0 0 15 0 4105 12 NO2 0 20 90 0 0 100 0...

Page 16: ...ited to the cost of the equipment The purchaser must obtain shipping instructions for the prepaid return of any item under this warranty provision and compli ance with such instruction shall be a cond...

Page 17: ...e end of its adjustment range Appendix B L C D Readout Calibration Procedure The 3 1 2 digit LCD meter span and decimal points may be configured for full scale ranges such as 1 100 0 25 0 10 0 0 1000...

Page 18: ...ion of calibration gas must be less than the factor number listed on Table 1 The formula for calibration is as follows Display Cal gas Factor where Display the span gas applied Cal gas is the percent...

Page 19: ...methylformamide 46 83 Ethyl Formate 44 80 Ethylmercaptan 56 102 n Heptane 39 70 n Hexane 37 67 Hydrazine 45 82 Hydrogencyanide 48 86 Hydrogen 77 139 Hydrogen Sulfide 41 74 Methane 100 181 Methyl Actet...

Reviews:

Related manuals for 4105 SERIES Applicability & effectivity