 Instruction Manual

Model 4105 Gas Sensor Module (12/02)

Page:  1

1.

PRODUCT DESCRIPTION

1.1 Introduction

Model 4105 Series Gas Sensor module features non-
intrusive calibration, 4-20 mA output signal and local
continuous display of the gas concentration in ppm
(toxics), % LEL (Combustibles), or % vol (Oxygen).  It
is designed for use with industry standard control in-
struments.

This manual provides instructions for 4105 series gas
sensor modules that utilize common packaging and
transmitter electronics with different sensors for de-
tection of various gases.  The full model number of
the gas sensor module includes a suffix, 4105-XX,
where “XX” is a number that identifies a gas type.

1.2 Application

The Model 4105-XX Gas sensor is intended for use in
ambient monitoring applications.  It is designed for
fixed installation and for continuous operation.

Optional fittings and adapters can be supplied by Si-
erra Monitor to provide continuous sample delivery
to the sensor module.

1.3 Configuration

The gas monitor is comprised of a NEMA-7/4 enclo-
sure which contains the transmitter electronics and a
gas sensor which is installed in one of the two 3/4"
conduit hubs.

1.3.1  Electronics

When installed, the transmitter electronics will be con-
nected to a power supply and control device via three
wire cable.

The electronics provide a 4-20 mA current loop which
is proportional to the full sensitivity of the sensor.
Integral features include:

-

L.C.D. readout of ppm of gas concentration.

-

Magnetic switches for non-intrusive calibration.

-

Visual indicators for fault condition.

-

Electrical fault (0 mA) to controller.

The transmitter electronics assembly includes a
printed circuit assembly and a cover plate which con-
tains the L.C.D. readout and magnetic switches for
calibration.

1.3.2  Sensor

The gas sensor cell is enclosed in a threaded housing
and is plugged into a signal card located in the enclo-
sure.  This configuration allows for easy field replace-
ment of the sensor cell.

Combustible:  The gas sensor is a catalytic bead type.

Toxics & Oxygen:  The gas sensor is an Electro Chemi-
cal type.

Figure 1.1 Model 4105 Gas Sensor Module

Figure 1.2 Outline View - Gas Sensor Module

5.42"

2.81"

1.75"

5.50"

4.50"

7.25"

Unity

SPAN

ZERO

FAULT /KEYPAD

CAL

Milpitas, CA

Ph. 408-262-6611

MODEL 4105-02

  

Combustibles

% LEL

Summary of Contents for 4105 SERIES Applicability & effectivity

Page 1: ...MODEL 4105 SERIES GAS SENSOR MODULE WITH DIGITAL DISPLAYAND NON INTRUSIVE CALIBRATION 4 20 mA...

Page 2: ...n 4105 05 Hydrogen Sulfide Gas Sensor Module with Non Intrusive Calibration 4105 06 Chlorine Gas Sensor Module with Non Intrusive Calibration 4105 07 Hydrogen Gas Sensor Module with Non Intrusive Cali...

Page 3: ...Transmitter Installation 3 3 6 Start up Operation 3 4 OPERATION 4 4 1 Introduction 4 4 2 Signal Value 4 5 CALIBRATION 5 5 1 Frequency of Calibration 5 5 2 Calibration Process 5 5 3 Equipment Required...

Page 4: ...which contains the transmitter electronics and a gas sensor which is installed in one of the two 3 4 conduit hubs 1 3 1 Electronics When installed the transmitter electronics will be con nected to a p...

Page 5: ...soldered Improperly spliced cable can result in corrosion resistance changes and system errors Wire Gauge Maximum Length 20AWG 2 000 Ft 18AWG 3 000 Ft 16AWG 4 000 Ft 14AWG 6 500 Ft 12AWG 9 000 Ft Tab...

Page 6: ...e moval and replacement of the sensor assembly which is threaded into the second 3 4 conduit hub 3 4 Wiring Connection To gain access to the I O PCB for wiring or mounting purposes loosen the two capt...

Page 7: ...r failure occurs Periodic cleaning as necessary Unanticipated maintenance 4 2 Signal Value During normal operation the current loop of the sen sor module and the controller will be between 4 mA indica...

Page 8: ...tic tool provided with each sensor Briefly hold the magnet tool close to the small dot located on the lower edge of the front panel The arrow on the upper left side of the LED will illuminate and the...

Page 9: ...new transmitter 7 Restore power and allow a minimum of 30 minutes for stabilization before re calibration 6 4 Sensor Replacement The sensor should be replaced when it is determined that It is no long...

Page 10: ...output at 0mA These conditions remain until the FAULT is corrected 6 4c Electrochemical Oxygen and Toxics Verify that the voltage VOUT is equal to the volt age as desired The VOUT test point on the I...

Page 11: ...facing vertically down The lid of the sensor module should face out for easy access Sensors may be mounted directly onto the end of a vertical conduit or bracketed to a vertical surface us ing the tw...

Page 12: ...VOLTS BAL R 2 R11 U1 Sensor Pwr Sig Black Brown Red Toxics P1 TB1 TB2 RIBBON CABLE TO CPU ASSY VOUT JP2 B A JP1 1 3 2 4 U2 U7 U4 U5 U1 S C R R19 ST 46A EC I O PCB FOR ELECTROCHEMICAL SENSORS Sensor Pw...

Page 13: ...F 14 to 122o F 14 to 122o F 14 to 122o F 14 to 122o F 10 to 75o C 7 to 50o C 10 to 50o C 10 to 50o C 10 to 50o C 10 to 50o C 10 to 50o C Relative Humidity 10 95 5 99 15 90 15 90 15 90 10 90 15 90 Pre...

Page 14: ...0 to 50o C 10 to 50o C 10 to 50o C 10 to 45o C 10 to 45o C Relative Humidity 15 90 15 90 15 90 20 90 20 90 Pressure 10 10 10 10 10 Electrical Data Input Voltage DC 19 30 VDC at less than 100 mA Output...

Page 15: ...0 55 30 2 40 50 4105 05 H2 S 0 5 100 20 0 1 15 15 0 0 0 0 4105 06 Cl2 0 10 100 0 0 105 0 0 0 0 4105 07 H2 1 20 0 100 3 0 35 3 35 85 4105 10 SO2 1 0 40 0 100 100 0 0 15 0 4105 12 NO2 0 20 90 0 0 100 0...

Page 16: ...ited to the cost of the equipment The purchaser must obtain shipping instructions for the prepaid return of any item under this warranty provision and compli ance with such instruction shall be a cond...

Page 17: ...e end of its adjustment range Appendix B L C D Readout Calibration Procedure The 3 1 2 digit LCD meter span and decimal points may be configured for full scale ranges such as 1 100 0 25 0 10 0 0 1000...

Page 18: ...ion of calibration gas must be less than the factor number listed on Table 1 The formula for calibration is as follows Display Cal gas Factor where Display the span gas applied Cal gas is the percent...

Page 19: ...methylformamide 46 83 Ethyl Formate 44 80 Ethylmercaptan 56 102 n Heptane 39 70 n Hexane 37 67 Hydrazine 45 82 Hydrogencyanide 48 86 Hydrogen 77 139 Hydrogen Sulfide 41 74 Methane 100 181 Methyl Actet...

Reviews:

Related manuals for 4105 SERIES Applicability & effectivity