background image

Model 4105 Gas Sensor Module (12/02)

Page:  8

 Instruction Manual

7.

INSTALLATION

7.1 Sensor Locations

Select locations for each of the sensors based on the
following:

-

Consider the density of the gas to determine
height of sensor above floor or ground level.

-

Sensors should be placed close to the potential
source of gas.

-

Sensors should be placed in areas accessible for
calibration.

-

Sensors must be pointed down and the conduit
should include an inverse trap to  reduce mois-
ture (condensation) from accumulating in the elec-
tronics enclosure.  See Figure 7.1.

7.2 Sensor Mounting

Where possible sensor modules should be installed
with the sensor facing vertically down.  The lid of the
sensor module should face out for easy access.

Sensors may be mounted directly onto the end of a
vertical conduit, or bracketed to a vertical surface us-
ing the two mounting flanges.  Insure that the body of
the enclosure is at least 1" from the wall so that the
sensor assembly can be rotated for removal and re-
placement.  See Figure 6.1 for installation configura-
tions.

7.3 Explosion Proof Installation

Where area classification requires explosion proof
(NEMA-7) installation a sealing fitting will be required
immediately above the gas sensor module enclosure.

7.4 Power Supply

The power supplied by the controlling device or an
external power supply must meet the following speci-
fications:

Voltage:

21-30 VDC

Current:

180 mA (Combustibles)
40 mA (Oxygen & Toxics)

Figure 7.1

Gas Sensor Module Installation

Summary of Contents for 4105 SERIES Applicability & effectivity

Page 1: ...MODEL 4105 SERIES GAS SENSOR MODULE WITH DIGITAL DISPLAYAND NON INTRUSIVE CALIBRATION 4 20 mA...

Page 2: ...n 4105 05 Hydrogen Sulfide Gas Sensor Module with Non Intrusive Calibration 4105 06 Chlorine Gas Sensor Module with Non Intrusive Calibration 4105 07 Hydrogen Gas Sensor Module with Non Intrusive Cali...

Page 3: ...Transmitter Installation 3 3 6 Start up Operation 3 4 OPERATION 4 4 1 Introduction 4 4 2 Signal Value 4 5 CALIBRATION 5 5 1 Frequency of Calibration 5 5 2 Calibration Process 5 5 3 Equipment Required...

Page 4: ...which contains the transmitter electronics and a gas sensor which is installed in one of the two 3 4 conduit hubs 1 3 1 Electronics When installed the transmitter electronics will be con nected to a p...

Page 5: ...soldered Improperly spliced cable can result in corrosion resistance changes and system errors Wire Gauge Maximum Length 20AWG 2 000 Ft 18AWG 3 000 Ft 16AWG 4 000 Ft 14AWG 6 500 Ft 12AWG 9 000 Ft Tab...

Page 6: ...e moval and replacement of the sensor assembly which is threaded into the second 3 4 conduit hub 3 4 Wiring Connection To gain access to the I O PCB for wiring or mounting purposes loosen the two capt...

Page 7: ...r failure occurs Periodic cleaning as necessary Unanticipated maintenance 4 2 Signal Value During normal operation the current loop of the sen sor module and the controller will be between 4 mA indica...

Page 8: ...tic tool provided with each sensor Briefly hold the magnet tool close to the small dot located on the lower edge of the front panel The arrow on the upper left side of the LED will illuminate and the...

Page 9: ...new transmitter 7 Restore power and allow a minimum of 30 minutes for stabilization before re calibration 6 4 Sensor Replacement The sensor should be replaced when it is determined that It is no long...

Page 10: ...output at 0mA These conditions remain until the FAULT is corrected 6 4c Electrochemical Oxygen and Toxics Verify that the voltage VOUT is equal to the volt age as desired The VOUT test point on the I...

Page 11: ...facing vertically down The lid of the sensor module should face out for easy access Sensors may be mounted directly onto the end of a vertical conduit or bracketed to a vertical surface us ing the tw...

Page 12: ...VOLTS BAL R 2 R11 U1 Sensor Pwr Sig Black Brown Red Toxics P1 TB1 TB2 RIBBON CABLE TO CPU ASSY VOUT JP2 B A JP1 1 3 2 4 U2 U7 U4 U5 U1 S C R R19 ST 46A EC I O PCB FOR ELECTROCHEMICAL SENSORS Sensor Pw...

Page 13: ...F 14 to 122o F 14 to 122o F 14 to 122o F 14 to 122o F 10 to 75o C 7 to 50o C 10 to 50o C 10 to 50o C 10 to 50o C 10 to 50o C 10 to 50o C Relative Humidity 10 95 5 99 15 90 15 90 15 90 10 90 15 90 Pre...

Page 14: ...0 to 50o C 10 to 50o C 10 to 50o C 10 to 45o C 10 to 45o C Relative Humidity 15 90 15 90 15 90 20 90 20 90 Pressure 10 10 10 10 10 Electrical Data Input Voltage DC 19 30 VDC at less than 100 mA Output...

Page 15: ...0 55 30 2 40 50 4105 05 H2 S 0 5 100 20 0 1 15 15 0 0 0 0 4105 06 Cl2 0 10 100 0 0 105 0 0 0 0 4105 07 H2 1 20 0 100 3 0 35 3 35 85 4105 10 SO2 1 0 40 0 100 100 0 0 15 0 4105 12 NO2 0 20 90 0 0 100 0...

Page 16: ...ited to the cost of the equipment The purchaser must obtain shipping instructions for the prepaid return of any item under this warranty provision and compli ance with such instruction shall be a cond...

Page 17: ...e end of its adjustment range Appendix B L C D Readout Calibration Procedure The 3 1 2 digit LCD meter span and decimal points may be configured for full scale ranges such as 1 100 0 25 0 10 0 0 1000...

Page 18: ...ion of calibration gas must be less than the factor number listed on Table 1 The formula for calibration is as follows Display Cal gas Factor where Display the span gas applied Cal gas is the percent...

Page 19: ...methylformamide 46 83 Ethyl Formate 44 80 Ethylmercaptan 56 102 n Heptane 39 70 n Hexane 37 67 Hydrazine 45 82 Hydrogencyanide 48 86 Hydrogen 77 139 Hydrogen Sulfide 41 74 Methane 100 181 Methyl Actet...

Reviews:

Related manuals for 4105 SERIES Applicability & effectivity