1 Summary
03.04.2006
Type of document
Document no.
Data Sheet “Bus Operator Unit RMZ792”
N3113
Installation Instructions “Bus Operator Unit RMZ792”
G3113
Environmental Declaration “Bus Operator Unit RMZ792”
E3113
Product range description “HVAC controllers with Konnex interface”
S3110
Basic Documentation “Communication with Konnex bus”
P3127
Data Sheet “Konnex bus KNX”
N3127
Synco™ 200 / Synco™ 700 Valid Version Set
J3100
CE Declaration of Conformity Synco 700
T3110
1.5 Key
features
Overview of outfit and functions of the RMZ792 bus operator unit:
Outfit / functions
RMZ792
Operating elements
Select-and-press knob (OK knob)
9
Info button to display information about the plant
9
Fault button for optical indication and acknowledgement
9
Backlit LCD (128×64 picture points)
9
Operation
Menu-driven operation in clear-text
9
Access levels
3
Password protection for each access level
9
Handling faults
Info page with clear-text display of faults
9
Visualization of faults with red LED
9
Display of all faulty devices with fault symbol
9
Remote acknowledgement and resetting of faults
9
Display of simultaneous faults (fault list)
20
Maximum number of bus users
150
User-defined favorite pages
Number of favorite pages
20
Number of datapoints per favorite page
10
Functions
Automatic device search run
9
Manual adding / removal of devices
9
Automatic / manual sorting of device list
9
Naming devices
9
Adding / removing / naming / sorting favorites
9
Exchangeable memory card (languages, device information)
9
Power supply
Konnex bus
9
Externally, AC 24 V
9
The following operating functions cannot be performed from the bus operator unit:
•
Access to the datapoints on the password level of the bus users (e.g. commissioning)
•
Display of trend graphs
•
Deletion of fault history
Note