8 General settings
03.04.2006
8.7
Password
Each of the 3 operating levels (
User level
,
Service level
and
Expert level
) can be protected
against unauthorized access through the use of passwords. The expert level is the
password level used by the bus operator unit. For the bus operator unit, the terms
“Password level” and “Expert level” have the
same
meaning.
Main menu > Settings > Passwords
Operating line
Range Factory
setting
User level
0…9999
0, that is, no
password
Service level
0…9999
0, that is, no
password
Expert level
1…9999
7
The passwords can only be changed on the password level. Setting value
0
means “no
password”, indicating that no password is required when accessing the respective
operating level.
The password required for the password level should be kept in a safe location! If the
password is lost, it will not be possible to retrieve the factory settings!
8.8 Device
list
Certain menus for editing the device list are available both on the password level and
the less protected service level. Functionality on the service level is restricted to sorting,
naming and renaming devices, and to selecting the way of presentation.
Main menu > Device list > Sort list
Main menu > Device list > Name devices
Main menu > Device list > Display list
Main menu > Device list > List information
The individual functions are described in chapter 5 “Commissioning”.
8.9 Favorite
pages
Certain menus for editing the favorite pages are available both on the password level
and the less protected service level. Functionality on the service level is restricted to
sorting, naming or renaming favorite pages and datapoints.
Main menu > Favorite pages > Name datapoints
Main menu > Favorite pages > Name favorites
Main menu > Favorite pages > Sort favorites
The individual functions are described in chapter 5 “Commissioning”.