3 Operation of devices
03.04.2006
Error / error message
Cause / remedy
Caution!
Device not responding
•
Communication with target device is not
possible
•
Is the device in operation?
•
Is the device connected to the Konnex
bus?
•
Has the device address been changed?
Datapoint shows a value that does
not make sense (e.g. room tempera-
ture 655.3 °C)
The device does not support information
describing what is visible; datapoint has no
meaning in the current configuration
Setting does not produce any effect
The device does not support information
describing what is visible; datapoint has no
meaning in the current configuration
3.7 User-defined
text
User-defined text from the devices is adopted, which means that the display on the bus
operator unit is identical with that on the local operator unit (RMZ790 / RMZ791). The
bus operator unit reads the user-defined text from the respective device. The RMZ792
displays the default text until the text from the device is received.