12.3 Average and maximum
DC 0…10 V signals to X1 and X2.
Task
Output average via Y1 and maximum via Y2 as DC 0…10 V signals.
CONF / INPUT X1 / LABEL
%
Configuration
CONF / INPUT X2 / LABEL
%
CONF / MIN-MAX-AVR / IN 1
X1
CONF / MIN-MAX-AVR / IN 2
X2
CONF / MIN-MAX-AVR / SPLIT
NO
CONF / MIN-MAX-AVR / MOD1AO1 Y1
CONF / MIN-MAX-AVR / TYP AO1
AVR
CONF / MIN-MAX-AVR / MOD1AO2 Y2
CONF / MIN-MAX-AVR / TYP AO2
MAX
12.4 Average from 6 input signals
2 passive temperature sensors LG-Ni 1000 connected to X1 and 1 passive
temperature sensor each connected to X2, X3, X4 and X5.
Task
Output average as a DC 0…10 V (0...50 °C) signal at Y1.
CONF / INPUT X1 / LABEL
TEMP
Configuration
CONF / INPUT X2 / LABEL
TEMP
CONF / INPUT X3 / LABEL
TEMP
CONF / INPUT X4 / LABEL
TEMP
CONF / INPUT X5 / LABEL
TEMP
CONF / MIN-MAX-AVR / IN 1
X1
CONF / MIN-MAX-AVR / IN 2
X2
CONF / MIN-MAX-AVR / IN 3
X3
CONF / MIN-MAX-AVR / IN 4
X4
CONF / MIN-MAX-AVR / IN 5
X5
CONF / MIN-MAX-AVR / MOD1AO1 Y1
CONF / MIN-MAX-AVR / TYP AO1
AVR
PARA / INPUT X1 / TYPE
2XNI
Setting values
PARA / INPUT X2 / TYPE
NI
PARA / INPUT X3 / TYPE
NI
PARA / INPUT X4 / TYPE
NI
PARA / INPUT X5 / TYPE
NI
PARA / MIN-MAX-AVR / FACTIN1
2
PARA / MIN-MAX-AVR / MINVAL1
0
PARA / MIN-MAX-AVR / MAXVAL1
50
PARA / MIN-MAX-AVR / MINVAL2
0
PARA / MIN-MAX-AVR / MAXVAL2
50
41 / 46
Siemens
SEZ220 signal converter
CE1P5146en
Building Technologies
Application examples
02.06.2008