7.4
Settings
Path:
COMMIS > CONF > ENTHALPY
Configuration
Display Name Settings
TEMP 1
Temperature input 1
---, X1...X5
RELHU 1
Relative humidity input 1
---, X1...X5
TEMP 2
Temperature input 2
---, X1...X5
RELHU 2
Relative humidity input 2
---, X1...X5
ENTH 1
Enthalpy 1
---, Y1, Y2
ABSHU 1
Absolute humidity 1
---, Y1, Y2
ENTH 2
Enthalpy 2
---, Y1, Y2
ABSHU 2
Absolute humidity 2
---, Y1, Y2
ENTH D
Enthalpy difference
---, Y1, Y2
DEWPNT
Dew point
---, Y1, Y2
Path:
... > PARA > MODE 2
Setting values
Display Name Unit
Range
Factory
setting
ALTIT Elevation
above sea
level
m
0…5000, adjustable in
increments of 10 m.
500
Path:
INFO
Display values
Display Name Comments
ENTH 1
Enthalpy 1
ABSHU 1
Absolute humidity 1
ENTH 2
Enthalpy 2
ABSHU 2
Absolute humidity 2
ENTH D
Enthalpy difference
DEWPNT Dew
point
Path:
COMMIS > TEST
Wiring test
Display Name Positions
ENTH 1
Enthalpy 1
---, 0...100 %
ABSHU 1
Absolute humidity 1
---, 0...100 %
ENTH 2
Enthalpy 2
---, 0...100 %
ABSHU 2
Absolute humidity 2
---, 0...100 %
ENTH D
Enthalpy difference
---, 0...100 %
DEWPNT
Dew point
---, 0...100 %
29 / 46
Siemens
SEZ220 signal converter
CE1P5146en
Building Technologies
Function block ENTHALPY
02.06.2008