Settings,
continued
Path:
INFO
Display values
Display Name
Comments
MIN 1
Minimum 1
Smallest value of the input signals assigned to
output Y1 (in the respective unit).
MAX 1
Maximum 1
Biggest value of the input signals assigned to
output Y1 (in the respective unit).
AVR 1
Average 1
Average value of the input signals assigned to
output Y1 (in the respective unit).
MIN 2
Minimum 2
Smallest value of the input signals assigned to
output Y2 (in the respective unit).
MAX 2
Maximum 2
Biggest value of the input signals assigned to
output Y2 (in the respective unit).
AVR 2
Average 2
Average value of the input signals assigned to
output Y2 (in the respective unit).
If setting values are defined for MINVAL and MAXVAL , Yx output signal does not
necessarily correspond to the displayed minimum and maximum values.
Note on MIN display
Example:
−
MINVAL1 is set to 20 °C.
−
The assigned input signals are 12 °C, 20 °C and 60 °C.
−
12 °C is displayed under MIN 1.
−
However, output signal Y1 is DC 0 V (because MINVAL = 20 °C).
Path:
COMMIS > TEST
Wiring test
Display Name
Positions
MOD1AO1 Min-max average output 1
---, 0...100 %
MOD1AO2 Min-max average output 2
---, 0...100 %
6.5
Error handling
A check identifies available input signals after quitting the COMMIS
(commissioning) menu. We differentiate between two cases if one of the input
signals previously acquired is missing due to short-circuit or open circuit:
Case
Description
Display
1
At least 1 input signal is
missing, but calculation is still
possible.
Fault symbol
. The calculated values are
displayed (Info pictures and INFO menu
(Inputs/outputs)).
2
At least 1 input signal is
missing, and calculation is not
possible.
Fault symbol
.
Values: MIN = 0; MAX = 0; AVR = 0.
The relevant input is not monitored if one of the input signals is missing after you
quit the COMMIS (commissioning) menu.
Section 5.4 describes how to handle errors of inputs Xx.
Note
27 / 46
Siemens
SEZ220 signal converter
CE1P5146en
Building Technologies
Function block MIN-MAX-AVR