Settings,
continued
Path:
... > COMMIS > TEST
Wiring test
Display Name
Positions
X1
X1
Display the current measured value at
terminal X1, non-adjustable.
… …
…
X5
X5
Display the current measured value at
terminal X5, non-adjustable.
Display. Name
Impact
Xx --- / ooo
Sensor error Xx
Non-urgent fault (Simple Alarm, Prio Low,
without plant stop).
Fault status messages
5.4
Error handling
When quitting the COMMIS (Commissioning) menu, the unit checks which input
signals are connected:
Monitor input signals
•
A sensor error message is displayed when one of these signals is subsequently
missing:
−
"Xx ---"
Signal missing (e.g. in the event of a cable break).
−
"Xx ooo"
Short-circuit (only applicable to passive signals).
•
Outputs are set to predetermined values when the function blocks are unable to
run calculations due to a missing input signal (see function block section “Error
handling“).
Changing the identifier for an inputs after the configuration for the other function
blocks is completed may cause certain functions for these blocks to become
inactive as otherwise they would have to operate on invalid units.
Exercise caution when
changing identifiers!
24 / 46
Siemens
SEZ220 signal converter
CE1P5146en
Building Technologies
Analog inputs X1…X5